AEG 400 KVA Manuale Utente

Pagina di 4
2
“Green” double  
protection for every 
application
VFI online double conversion 
topology in this equipment 
offers built-in inverter galvanic 
protection completely isolating 
the output power from all 
input power anomalies, 
delivering fully conditioned 
pure sine-wave output.
In pure on-line mode the unit 
delivers an excellent certified 
96 % efficiency. Because of 
the technology and topology 
used, no additional losses are 
generated to achieve low input 
harmonics or input / output 
galvanic isolation.
The Fluxpower HPS unit is 
designed to provide excellent 
output voltages suited to very 
demanding applications  
with either 100 % step load,  
unbalanced, non-linear  
or modern IT loads. It also  
provides exceptional  
performance: with a power 
factor of up to 0.9 (lagging  
or leading), there is no  
requirement to de-rate the unit.
Triple Intelligence
If the application requires 
extremely flexible and  
reliable UPS protection,  
the Fluxpower HPS is ideal.  
It delivers advanced features 
based on state-of-the-art total 
digital control. This control 
incorporates dual DSP (Digital 
Signal Processing) and µC 
(Micro controller) technologies.
The system design ensures that 
auxiliary power supplies and 
processors are no longer single 
points of failure which could 
compromise the availability 
of clean power to the load. 
The Fluxpower HPS is 
designed to overcome the 
limitations imposed by other 
older, designs. With its 
distributed control architecture,  
Fluxpower HPS will always 
have a UPS circuit protecting 
the load; furthermore, 
the status of most critical 
components is constantly 
monitored, allowing predictive 
maintenance and avoiding 
unexpected breakdowns.
Fluxpower HPS’ working state 
can be easily monitored by 
any Building Management 
System and via LAN / WAN.
Life-prolonging 
Battery Management
Batteries are electro-chemical 
devices, which store charge 
chemically; as such their 
performance degrades with 
time. The Fluxpower HPS owns 
a Battery Anti-Aging Control 
(BAAC) according to battery 
manufacturers’ requirements.
Following a UI characteristic 
curve, the charger charges at 
a constant current appropriate 
for the battery type used, 
preventing detrimental 
excess charging. In addition 
to the float voltage level, 
boost charge can be set, 
optimizing the recharge time 
when there is the possibility 
of consecutive power outages 
within a short period. 
BAAC also reduces the 
residual ripple current (one 
of the causes of premature 
battery wear), as well as 
protecting the battery from 
damaging deep discharges.
Automatic battery temperature 
compensation charge voltage 
may be implemented, 
charging the battery more 
appropriately and increasing 
battery life. By means of DCM 
(Dynamic Charging Mode) 
very long battery autonomies 
can be achieved without 
increasing total charge time. 
This is achieved through 
the implementation of an 
intelligent increase in maximum 
battery charge current when 
the maximum inverter power is 
not being drawn by the load.
An integrated periodical 
battery testing function tests 
and monitors battery health, 
providing advanced warning 
to guide the application of 
preventive maintenance.
Parallel systems  
with “hot swap” 
modularity
Fluxpower HPS UPS offers 
parallel options in both 
redundancy and capacity 
modes, providing the 
possibility for both extra 
system resilience and 
increased capacity.
The parallel control circuitry 
associated with these units 
is fully digital and acts on 
both active and reactive 
power on each of the three 
output phases. This allows 
accurate load current sharing 
among the UPS units even 
during transient conditions.
1.  Input mains (separate for by-pass and rectifier)
2.  Rectifier and battery charger
3.  External battery
4.  Inverter
5.  Emergency line (by-pass) with optional backfeed 
contactor
6.  Inverter (SSI) and by-pass (SSB) static switch
It is possible to install an external manual bypass, 
either in the matching cubicle or in wall mounted box 
(bypass switch auxiliary contact must be connected  
to UPS related input port for status monitoring).
FLUXPOWER HPS
3-PHASE UPS
1
2
3
F
F
+B  -B
3xL-N
3xL
PE
5
3xL-N
F
OPTIONAL (External Manual bypass)
4
6