Operating Manual LP 33 Series 30 & 40 kVA 
Manual bypass operation 
 
The manual bypass circuit consisting of Q1 and 
Q2 manual switches, permits the transfer of the 
load directly to the mains without interruption, 
leaving the UPS galvanically separated from the 
output load
 
This type of operation is normally used when the 
UPS system must be completely turned off for 
maintenance or reparation. 
 
Fig. 3.2-5   Energy flow in manual bypass operation 
 
 
 
 
Mains failure operation 
 
In the event of a mains power failure, the 
rectifier and the battery-charger turn OFF, 
while the inverter continues to supply the load 
without interruption using the energy stored in 
the battery
 
During the battery discharge, the LCD screen 
displays the remaining autonomy, based on the 
battery capacity and the applied load
 
Fig. 3.2-6   Energy flow during mains failure operation 
 
In the event of an extended mains failure, before the battery is fully discharged, the alarm “stop 
operation” warns the user that the UPS will start the shutdown procedures when the indicated time 
expired (normally 3 minutes). 
 
 
     In case of parallel system 
 
With parallel system for power capacity
 
•  With the bypass mains power available as the warning “battery low” occurs on one unit, after 
timeout (selectable) the load is transferred to mains. 
•  With  missing bypass mains power as the warning occurs on one unit, the system starts the 
timeout (selectable) of “Stop operation” and then the output load shuts down. 
 
 
With redundant parallel system
 
•  As the warning battery low occurs on one unit unnecessary to support the present load, after 
timeout (selectable) this unit shuts down and the load is shared between the other units. 
As the warning occurs on one unit necessary to support the present load, the system starts the 
timeout (selectable) of “stop operation” and then the output load shuts down.