Operating Manual LP 33 Series 30 & 40 kVA 
Code 
Message 
Meaning 
 
4602 
Q1 
OPEN 
The auxiliary contact indicates that the output switch Q1 has 
been opened. 
4603 
Q1 
CLOSED 
The auxiliary contact indicates that the output switch Q1 has 
been closed. 
4699 
BATTERY TEST 
IMPOSSIBLE 
Not possible to start battery test (it is postponed) for: 
•  No mains rectifier or bypass; 
•  Battery not fully charged; 
•  Load is below 10% or above 80%. 
4763 
REMOTE CONTROL 
ON 
Inverter can be started or shutdown by remote control.  
Commands source can be chosen depending on the value of 
respective parameter (password required): 
0  =  Only local panel. 
1  =  Only serial port on CI (TLC). 
2 =  Both. 
4764 
REMOTE CONTROL 
OFF 
Inverter can be started or shutdown by remote control.  
Commands source can be chosen depending on the value of 
respective parameter (password required): 
0  =  Only local panel. 
1  =  Only serial port on CI (TLC). 
2 =  Both.