Modifications reserved 
Page 36/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
3.  Switch On the output switch Q1 (Pos. I)
The output will be supplied by the mains through the bypass. 
 
LP 33          40kVA 
APPLICAT. ON UTILITY 
= 70% 
 
 
Verify, selecting the screen METERING/Udcp and Udcn, that the 
booster voltage has reached about 215 VDC. 
 
Udcp=215V Udcn=215V 
Ubp=164V Ubn=164V 
 
 
Charge level 
=  100% 
Autonomy = 
800min 
 
4.  Switch On the inverter entering the screen: 
MENU/COMMAND MENU/INVERTER ON 
 
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
 
Some seconds later the load will be transferred on inverter 
and the main screen will display: APPLICATION ON UPS 
 
LP 33          40kVA 
APPLICATION ON UPS 
= 70% 
 
 
5.  Operation mode selection
LP 33 Series is delivered normally selected for permanent VFI operation. 
ECO Mode can be enabled and the ECO START time & ECO STOP time can be programmed for each
day of the week (see Section 6.3.1-5).
 
 
END OF PROCEDURE 
 
 
 
 
 
 
 
NOTE ! 
Even if the UPS is delivered with the battery fully charged, they could be partially 
discharged during transportation or storage. 
It is recommended to recharge the battery during a few hours in order to provide the 
complete battery
 energy stored to the load in the event of mains failure.