GE AF-300 Manuale Utente

Pagina di 98
-26- 
4) Connection to PLC (when analog signal is input from PLC)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
12 
V
 
U
 
W
 
13 
FWD 
11 
X1
 
REV
 
CM
 
X3
 
30C 
30B 
30A 
X2 
(THR)
 
L2/S
 
L1/R
 
L3/T
 
P1
 
P(+)
 
N(-)
 
P(+)
 
M
FM
 
C1 
MCCB 
Frequency setting voltage input 
+10Vdc
 
250
Ω
 
4.7k
Ω
 
22k
Ω
 
Pulse output  
 
0V
 
0V
 
Analog monitor
 
Alarm output for any fault
 
To 11 terminal 
Analog meter
 
G 
G 
+24 to +27Vdc 
P L C 
24Vdc
To external thermal relay 
External thermal relay
 
To X2 terminal  
  To CM terminal
 
X3
 
EXT
 
INT
 
PLC
 
SW7 
*1 
When the PLC power supply common may be connected to the drive 11 terminal to input analog frequency setting 
signals from the PLC, use this connection and set the SW7 switch 1 to EXT and 2 to PLC to prevent the FWD and 
REV terminals from turning on due to sneak path current when the PLC power is turned off. 
*2 
With this connection, the power is supplied from the PLC power supply to the external thermal O/L relay.  So, OH2 trip 
is activated by PLC power-off with the drive turned on. 
*3 
To prevent drive trip with OH2 when the PLC power being turned off, do not select the THR te rminal function and use 
the drive electronic thermal O/L relay. 
*4 
When the X3 terminal is used as the PLC terminal, no function that can be set with E03 can be used.  The X3 terminal 
is dedicated to the PLC
24 V dc : 
PLC power supply
 
Figure 2-3-12  Connection example of PLC terminal (when analog signal is input from PLC) 
To ground terminal
 
L1/L 
L2/N 
3-phase 230V 
input series
 
200 to 230V  
50/60Hz 
Single-phase 
230V input series
200 to 240V  
50/60Hz 
MCCB 
INT
 
EXT
 
PLC
 
X3
 
STOP 
RUN
 
PRG 
RESET
 
FUNC 
DATA
 
3~ 
FUSE 
FUSE