  Trial Run 
The motor rotates when a frequency value and running command are input from the keypad   
 panel or external signal terminal.  Refer to Table 3-3-1. 
Use a low frequency (about 5Hz) for trial runs 
A frequency can be set using the built-in frequency setting POT (VR) , and forward/stop  
 can be performed using the keypad panel with the functions set in the factory. 
Table 3-3-1  Running command 
Operation method 
Frequency setting 
Running command 
Operation by using 
keypad panel 
Operation starts when the 
RUN key is pressed. 
 The motor decelerates and 
stops when the STOP key is 
pressed. 
 
 
Operation by using 
external signal ter-
minal 
 
 
(When built-in POT (VR) is used) 
The frequency increases when the variable 
resistor is turned clockwise and reduces 
when it is turned counterclockwise.  The mo-
tor accelerates when the variable resistor  is 
turned clockwise during operation and de-
celerates when it is turned counterclockwise. 
 
(When the UP/DOWN key is used) 
Frequency increases when the UP key is 
pressed. 
It reduces when the DOWN key is pressed. 
Operation starts when FWD 
(REV) terminal is connected. 
The motor decelerates and 
stops when the FWD (REV) 
terminal is disconnected. 
* Operation is not stopped 
although the STOP key is 
pressed. (When the data of 
F02 is set to “2” or “4”) 
 
Check the following items: 
  a)    Rotation direction 
  b)    Whether rotation is smooth (whether there is a motor buzzing noise or abnormal vibration) 
  c)    Whether acceleration and deceleration are smooth 
  d)    Whether the drive cooling fan is rotating (1.5kW or more) 
If no abnormality is detected, check the item again by increasing the frequency. 
Even if the output from the drive is stopped, you will be get an electric shock when you touch the main 
circuit terminals such as drive output terminals U, V and W if the voltage is supplied to the main power 
supply input terminal. 
The smoothing capacitor in the drive has been charged when the power is turned off and it is not dis-
charged immediately.  Before touching the electric circuit, wait until at least five minutes have elapsed 
after power-off and the charge lump is off, indicating the voltage is already low. 
After checking normality in the above trial run, start operation.