Tyco 4100U Manuale Utente

Pagina di 180
 
2-27
 
 
The 4100-0632 Terminal Block Utility Module is an all-purpose terminal block that 
mounts to an expansion bay, above or below the power distribution interface (PDI). Each 
module utilizes one block of mounting space. 
 
The terminal block utility module has two 16-position terminal blocks that accept up to a 
maximum of 12 AWG (3.309 mm
2
) wire. 
 
Follow the directions below to mount the terminal block utility module to the electronics 
bay. 
 
1.  Align the terminal block utility module to any two compatible screw holes on the 
electronics bay. Position the higher terminal block towards the middle of the 
bay.  There are eight possible locations: four above and four below the PDI. 
Refer to the figure, below. 
2.  Secure the terminal block utility module to the electronics bay with two #6 
screws and lockwashers. 
3.  The shorting strip may be removed or modified, depending on the application. 
 
Figure 2-20. Terminal Block Utility Module Mounting 
 
 
 
The Terminal Block Utility Module (4100U) 
Overview 
Mounting to the 
Electronics Bay 
TERMINAL BLOCK UTILITY MODULE 
#6 SCREW AND LOCKWASHER 
SCREW HOLES FOR
MODULE BRACKET
SCREW HOLES FOR 
MODULE BRACKET