Chapter 6  Control Modes of Operation|ASDA-B Series
 
6-12  
 
Revision January, 2009
 
Settings: 
It is used to determine the acceleration time to accelerate from 0 to its rated rotation speed. 
(When P1-36 is set to 0: Accel/Decel function is disabled, i.e. P1-34, P1-35 is disabled) 
 
P1 - 35 
  TDEC  Deceleration Time 
Communication Addr.: 0123H
Default: 200 
Related Section:  
Applicable Control Mode: S 
P1-34, P1-36, Section 6.3.3 
Unit: ms 
Range: 1 ~ 20000 
Settings: 
It is used to determine the deceleration time to decelerate from its rated rotation speed to 0. 
(When P1-36 is set to 0: Accel/Decel function is disabled, i.e. P1-34, P1-35 is disabled) 
 
P1 - 36 
  TSL 
Accel /Decel S-curve 
Communication Addr.: 0124H
Default: 0 
Related Section:  
Applicable Control Mode: S 
P1-34, P1-35, Section 6.3.3 
Unit: ms 
Range: 0 ~ 10000 (0: Disabled)  
Settings: 
This parameter is used to make the motor run more smoothly when startup and windup. 
Using this parameter can improve the motor running stability. 
Time
(ms)
Speed
TSL/2
TACC
TSL/2
TSL/2
TDEC
TSL/2
 
TSL: P1-36, Accel /Decel S-curve 
Total acceleration time = TACC + TSL 
TACC: P1-34, Acceleration time 
Total deceleration time = TDEC + TSL 
TDEC: P1-35, Deceleration time 
NOTE
 
1)  If the setting value of parameter P1-36 is set to 0, it indicates Accel / Decel S-curve function 
is disabled and the command is just By-Pass.