Do not share the external supply voltages (the V and C 
terminals) with other devices (including other FieldPoint 
devices), unless those devices are isolated from human contact.
You must connect the protective earth (PE) ground terminal on 
the cFP-BP-x backplane to the system safety ground. The 
backplane PE ground terminal has the following symbol 
stamped beside it: 
. Connect the backplane PE ground 
terminal to the system safety ground using 14 AWG (1.6 mm) 
wire with a ring lug. Use the 5/16 in. panhead screw shipped 
with the backplane to secure the ring lug to the backplane PE 
ground terminal.
As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes and 
commonsense practices. Mount backplanes in an area, 
position, or cabinet that prevents accidental or unauthorized 
access to wiring that carries hazardous voltages.
The isolation of the cFP-RLY-421 is certified as 
double-insulated for working voltages of 250 V
rms
. Do not use 
the cFP-RLY-421 as the only isolating barrier between human 
contact and working voltages of more than 250 V
rms
.
Operate the cFP-RLY-421 only at or below Pollution Degree 2. 
Pollution Degree 2 means that only nonconductive pollution 
occurs in most cases. Occasionally, however, a temporary 
conductivity caused by condensation must be expected.
Do not operate FieldPoint products in an explosive atmosphere 
or where there may be flammable gases or fumes. If you need 
to operate FieldPoint products in such an environment, the 
FieldPoint products must be in a suitably rated enclosure.
Operate the cFP-RLY-421 at or below Installation Category II. 
Installation Category II is for measurements performed on 
circuits directly connected to the low-voltage installation. 
This category refers to local-level distribution, such as that 
provided by a standard wall outlet.