CFM UVHK29MN Manuale Utente

Pagina di 20
12
20008056
NOTE:  To determine the size of the branch gas line from the main gas line to the fireplace, enter the tables below (for 
iron pipe or copper tubing) using the distance from the gas meter or second stage regulator to the furthest appliance on 
the gas system.  Select a pipe or tube diameter which has enough capacity to meet the maximum input requirement of 
the fireplace.  Regardless, do not use less than 1/2” diameter for the branch line.  For any distances required longer than 
shown in these tables, refer to the National Fuel Gas Code.
NOTE:  There may be a local gas utility requirement specifying a minimum diameter for gas piping.  All units require a 1/2 inch pipe con-
nection at the gas valve.
Gas Line Pipe Sizing
CAPACITY OF PIPING
Cubic Feet per Hour based on 0.3” w.c. Pressure Drop
Specific Gravity for Natural Gas - 0.6 (1000 BTU/Cubic Foot)
Specific Gravity for Propane Gas - 1.6 (2550 BTU/Cubic Foot)
Gas Pressure Check
Check the inlet pressure to the appliance to ensure that it is as 
shown in Table 1.  Also check the incoming gas pressure where 
the field installed gas line connects to the gas logs.
The manifold pressure is controlled by the regulator and should 
be checked at the pressure test point located downstream from 
the regulator on the control valve body.  Access to the pressure 
test point is obtained by removing all logs and the heat shield 
on the right hand rear side of the base.  The pressure test point 
1/8” NPT plugged tapping is located on the rear face of the 
control body.  (Fig. 5)
The pressure should be checked with the appliance burning on 
high (highest setting) and all other gas appliances turned on.  
One must then read the manometer and if pressures are not 
10” w.c. for LP or 3.5” w.c. for natural gas, then the inlet pres-
sure must be adjusted or increased until the proper pressures 
are attained.  If these pressures are greater than 10” w.c. for 
LP or 3.5” w.c. for natural gas, contact your gas supplier before 
operating the appliance.
The pressure regulator is preset and locked to prevent tamper-
ing.  If the pressure is not  as specified, replace the regulator 
with part # 73332 (for natural gas only), or part # 73333 (for L.P. 
gas only).
CAUTION:  If the appliance’s operating pressures are not 
checked and adjusted, improper combustion may result in soot 
being produced.
After measuring the pressure, replace the test point plug and 
check for leaks.  Replace the control box cover and the two 
phillips head screws.
 
Length 
Nominal Inches for Iron Pipe Sizes (1,000s BTU/hr)
 
of 
1/2” D 
3/4” D 
1” D 
1¹⁄₄” D 
1¹⁄₂” D
 
Pipe 
Natural  Propane  Natural  Propane  Natural  Propane  Natural 
Propane  Natural  Propane
 
20’ 
92 
143 
190 
296 
350 
546 
730 
1135 
1100 
1711
 
30’ 
73 
115 
152 
237 
285 
444 
590 
918 
890 
1385
 
40’ 
63 
97 
130 
202 
245 
380 
500 
778 
760 
1183
 
50’ 
56 
87 
115 
179 
215 
334 
440 
683 
670 
1043
 
60’ 
50 
79 
105 
163 
196 
304 
400 
622 
610 
949
 
70’ 
46 
71 
96 
151 
180 
280 
370 
576 
560 
872
 
90’ 
40 
61 
84 
130 
160 
250 
320 
497 
490 
763
 
100’ 
38 
59 
79 
122 
150 
235 
305 
474 
460 
717
 
Outside Diameter Copper Tubing, Type L (1,000s BTU/hr)
 
Tubing Length 
1/2” 
5/8” 
3/4” 
7/8”
 
Feet 
0.43 
0.545 
0.666 
0.785
 
10 
110 
206 
348 
536
 
20 
76 
141 
239 
368
 
30 
61 
114 
192 
296
 
40 
52 
97 
164 
256
 
50 
46 
86 
146 
224
 
60 
42 
78 
132 
203
 
80 
36 
67 
113 
174
 
100 
32 
59 
100 
154
WARNING: Use only internally tinned copper tubing. If correct copper tubing is not used, tubing can deteriorate and develop 
gas leaks.
T126
Test point
10/29/03   djt
 
Table 1 
 
Gas Inlet Pressure  
Natural  
Propane
 
Max. 
10.5” w.c. 
13” w.c.
 
Normal 
7” w.c. 
11” w.c.
 
Min.* 
5.5” w.c. 
11” w.c.
 
Regulator Pressure 
3.5” w.c. 
10.0” w.c.
*Minimum inlet supply pressure for the purpose of input adjustment.
Test Point
T126
Fig. 5  Pressure test point.