2000 Autoflow
50
Master to Slave Interconnect
A slave fan/heater unit can be added to oper-
ate in unison with the master fan/heater unit.
The interconnect between the master and slave
fan/heater units remains the same regardless
of the type or presence of a control center. To
wire a slave fan/heater unit to a master fan/
heater unit do the following:
NOTE: Do NOT use solid wire for intercon-
nection.
1. Run four (4) 16ga MTW type wires from
the master fan/heater  unit to the slave fan/
heater unit.
2. Connect the wires as shown in figure #26.
Figure 26: Wiring for a  slave fan/heater unit to a master fan/heater unit.
ELECTRICAL POWER SUPPLY
NOTE: A shielded 16 gauge cable is recom-
mended for use on the network connections.
The network connections for this configura-
tion are attached to terminals number 8 and 9
in the master unit and terminals number 3 and
4 in the slave unit.  Ground each end of the
shielded cable to the housing.  A shielded 16
gauge 2 wire cable can be purchased from GSI.
Part # WR-16 / 2S.