Honeywell PUB4024S ユーザーズマニュアル

ページ / 24
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
63-2689—05
8
required and thereby affect transformer sizing. The following 
example is an I x R line-loss calculation for a 200 ft. (61m) run 
from the transformer to a controller drawing 37 VA and using 
two 18 AWG (1.0 sq mm) wires.
The formula is:
Loss = [length of round-trip wire run (ft.)] x [resistance in 
wire (ohms per ft.)] x [current in wire (amperes)]
From specification data:
18 AWG twisted pair wire has a resistance of 6.52 ohms per 
1000 feet.
Loss = [(400 ft.) x (6.52/1000 ohms per ft.)] x [(37 VA)/(24V)] 
= 4.02 volts
This means that four volts are going to be lost between the 
transformer and the controller. To assure the controller 
receives at least 20 volts, the transformer must output more 
than 24 volts. Because all transformer output voltage levels 
depend on the size of the connected load, a larger transformer 
outputs a higher voltage than a smaller one for a given load. 
Fig. 10 shows this voltage load dependence.
In the preceding I x R loss example, even though the controller 
load is only 37 VA, a standard 40 VA transformer is not 
sufficient due to the line-loss. Looking at Fig. 10, a 40 V
transformer is just under 100 percent loaded (for the 37 VA 
controller) and has a secondary voltage of 22.9 volts. (Use the 
lower edge of the shaded zone in Fig. 10 that represents the 
worst case conditions.) When the I x R loss of four volts is 
subtracted, only 18.9 volts reaches the controller. This is not 
enough voltage for proper operation.
In this situation, the engineer has three alternatives:
1. Use a larger transformer. For example, if an 80 VA model 
is used, an output of 24.4 volts, minus the four volt line-
loss, supplies 20.4V to the controller (see Fig. 10). 
Although acceptable, the four-volt line-loss in this exam-
ple is higher than recommended.
IMPORTANT
No installation should be designed where the line-loss 
is greater than two volts. This allows for nominal oper-
ation if the primary voltage drops to 102 Vac (120 Vac 
minus 15 percent).
2. Use heavier gauge wire for the power run. 14 AWG 
(2.0 sq mm) wire has a resistance of 2.57 ohms per 
1,000 ft. Using the preceding formula results in a line-
loss of only 1.58 volts (compared with 4.02 volts). This 
would allow a 40 VA transformer to be used. 14 AWG 
(2.0 sq mm) wire is the recommended wire size for 24 
Vac wiring.
3. Locate the transformer closer to the controller. This 
reduces the length of the wire run, and the line-loss.
The issue of line-loss is also important in the case of the output 
wiring connected to the Triac digital outputs. The same formula 
and method are used. Keep all power and output wire runs as 
short as practical. When necessary, use heavier gauge wire, a 
bigger transformer, or install the transformer closer to the 
controller.
To meet the National Electrical Manufacturers Association 
(NEMA) standards, a transformer must stay within the NEMA 
limits. The chart in Fig. 10 shows the required limits at various 
loads.
With 100 percent load, the transformer secondary must supply 
between 23 and 25 volts to meet the NEMA standard. When a 
purchased transformer meets the NEMA standard DC20-1986, 
the transformer voltage regulating ability can be considered 
reliable. Compliance with the NEMA standard is voluntary.
Fig. 10. NEMA Class 2 transformer voltage output limits.
The Honeywell transformers listed in Table 5 meet the NEMA 
standard DC20-1986.
Table 5. Honeywell transformers that meet 
NEMA standard DC20-1986.
NOTE: The AT88A and AT92A transformers do not meet 
the voluntary NEMA standard DC20-1986.
Wiring
All wiring must comply with applicable electrical codes and 
ordinances, or as specified on installation wiring diagrams. 
Controller wiring is terminated to the screw terminal blocks 
located on the top and the bottom of the device.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or 
making wiring connections, to prevent electrical shock 
or equipment damage.
NOTES:
For multiple controllers operating from a single 
transformer, the same side of the transformer 
secondary must be connected to the same power 
input terminal in each controller. Controller 
configurations will not necessarily be limited to 
three devices, but the total power draw, including 
accessories, cannot exceed 100 VA when 
powered by the same transformer (U.S. only). For 
power and wiring recommendations, See “Power” 
Transformer Type
VA Rating
AT40A
40
AT72D
40
AT87A
50
AK3310 Assembly
100
27
26
25
24
23
22
21
20
19
18
17
16
15
14
0
50
100
150 
% OF LOAD
SECONDAR
Y
 VOL
TAGE
200 
M993