Mitsubishi Electronics FX5 ユーザーズマニュアル

ページ / 306
198
19  BUILT-IN I/O FUNCTION
19.7  PWM Function
Period
The period of PWM output is stored.
Corresponding devices
The device numbers corresponding to each channel are as follows.
Update timing
The timing to reflect the device in operation is as follows.
 • When the HCMOV instruction is executed (values updated immediately)
 • When the PWM instruction is executed
 • END processing
Clear timing
The timing when the device is cleared is as follows.
  • STOP/PAUSE
RUN
 • The pulse width and cycle can be changed even while pulses are being output.
 • The pulse width and cycle are stored in the unit specified by the parameter (ms or 
s).
Number of output pulses current value monitor
The current value of the number of output pulses of PWM output is stored.
Corresponding devices
The device numbers corresponding to each channel are as follows.
Update timing
The timing to reflect the device in operation is as follows.
 • When the HCMOV instruction is executed (values updated immediately)
 • When the PWM instruction is executed
 • END processing
Clear timing
The timing when the device is cleared is as follows.
  • Power  OFF
ON
 • Reset
  • STOP/PAUSE
RUN
 • If the number of output pulses is set to "0" (output without any limitation), the number of output pulse current 
value monitor is fixed at "0".
 • The number of output pulse current value monitor can be changed even while pulses are being output.
CH1
CH2
CH3
CH4
SD5305, SD5304
SD5321, SD5320
SD5337, SD5336
SD5353, SD5352
CH1
CH2
CH3
CH4
SD5307, SD5306
SD5323, SD5322
SD5339, SD5338
SD5355, SD5354