9  PID CONTROL FUNCTION
9.8  Examples of Program
75
9
Program
OUTHS
ST0
K2000
MOV
SM402
Initial pulse
SM402
Initial pulse
SM402
Initial pulse
X011
PID control 
is started
M3
PID operation 
is executed
ST0
Heater operation 
cycle
M3
PID operation 
is executed
M3
PID operation 
is executed
ST0<D502
X011
PID control 
is started
MOV
MOV
MOV
MOV
MOV
MOV
SD6022
K5000
K500
SET
SET
K2000
K0
K3000
K2000
K5000
RST
RST
D510
PID
<  ST0 D502
D500
RST
D500
The target value is 
set to 50°C
The sampling time is 
set to 500 ms
The operation direction 
is set to backward 
operation
The upper and lower 
limits of output value 
is set to valid
The output value upper 
limit is set to ON for 2 sec.
PID instruction initial setting
Built-in analog monitor
   CH1: SD6022
   CH2: SD6062
0: Enable
1: Disable
Heater output control
The output value lower 
limit is set to ON for 0 sec.
The proportional gain is 
set to 3000 %
The integral time is set to 
2000×100ms
The differential time is 
set to 5000×100ms
The built-in analog is set to used CH.
   CH1: SM6021
   CH2: SM6061
The PID output is initialized
PID instruction 
drive
PID operation is executed
The heater operation 
cycle is set to 2 sec
Preset
Heater output
D510
D511.0
D511.5
D532
D533
D513
D514
D516
SM6021
D502
D502
M3
ST0
Y1
END