9  PID CONTROL FUNCTION
9.8  Examples of Program
83
9
Program
OUTHS
ST0
K2000
MOV
SM402
Initial pulse
SM402
Initial pulse
Initial pulse
SM402
PID control is started 
after auto-tuning
PID is executed
PID is executed
X010
PID control is started 
after auto-tuning
X011
PID control is started 
(without auto-tuning)
M4
ST0
Heater operation 
cycle
M4
PID control is started 
(without auto-tuning)
X011
M4
Auto-tuning is executed
ST0<D502
X010
MOV
SD6022
K5000
K500
SET
SET
K0
MOV
RST
RST
D510
PID
<  ST0 D502
D500
RST
D500
The target value is set to 50°C
The sampling time is set to 
500 ms
The operation direction is 
set to backward operation
PID instruction 
initial setting
Built-in analog monitor
   CH1: SD6022
   CH2: SD6062
0: Enable
1: Disable
Heater output control
The upper and lower limits of 
output value is set to valid
The output value lower limit 
is set to ON for 0 sec.
The built-in analog is set to used CH
   CH1: SM6021
   CH2: SM6061
The PID output is initialized
PID instruction drive
PID is executed
The heater operation 
cycle is set to 2 sec.
Preset
Heater output
D510
D511.0
D511.5
K2000
MOV
The output value upper limit 
is set to ON for 2 sec.
D532
D533
SM6021
D502
D502
M4
ST0
Y1
END
X010
PID control is started 
after auto-tuning
RST
K1800
MOV
SET
D511.6
The auto-tuning is set to 
step response method
The output of auto-tuning 
is set to 1.8 sec.
Auto-tuning initial 
setting
Auto-tuning is executed
D536
D511.4