Mitsubishi Electronics LY18R2A ユーザーズマニュアル
41
CHAPTER 4 SPECIFICATIONS
4
4.
3
O
O
u
tput
Mo
Mo
dul
e
e
Spe
cif
icat
ions
ions
4.3.3
LY20S6 triac output module
Item
Specifications
Appearance
Number of output points
16 points
Rated load voltage,
frequency
frequency
100 to 240VAC (+10%/-15%), 50/60Hz(±3Hz)
Maximum load current
0.6A/point, 4.8A/common
Load voltage distortion ratio
Within 5%
Maximum load voltage
264VAC
Minimum load
voltage/current
voltage/current
24VAC/100mA, 100VAC/25mA, 240VAC/25mA
Maximum inrush current
20A/cycle or less
Leakage current at OFF
3mA or lower (at 240V, 60Hz), 1.5mA or lower (at 120V, 60Hz)
Maximum voltage drop at ON
1.5V or lower (at load current of 0.6A)
Response
time
time
OFF to ON
Total of 1ms and 0.5 cycles or less
ON to OFF
Total of 1ms and 0.5 cycles or less (rated load, resistive load)
Surge suppressor
CR absorber
Fuse
None (Attaching a fuse to each external wiring is recommended.)
Dielectric withstand voltage
2300VAC, 1 minute (altitude 2000m)
Insulation resistance
10M
or more by insulation resistance tester
Noise immunity
By noise simulator of 1500Vp-p noise voltage, 1µs noise width and 25 to 60Hz noise
frequency
frequency
Protection degree
IP1X
Common terminal
arrangement
arrangement
16 points/common (common terminal: TB17)
Number of occupied I/O
points
points
16 points (I/O assignment: output 16 points)
External interface
18-point screw terminal block (M3 × 6 screws)(
5VDC internal current
consumption
consumption
300mA (TYP. all points ON)
Weight
0.22kg
External connections
Terminal connections
Load
Load
TB16
LED
TB17
100 to 240VAC
LED
TB1
Internal
circuit
Terminal
number
Signal
name
Signal
name
Viewed from the front of the module.
Y01
Y03
Y05
Y07
Y09
Y0B
Y0D
Y0F
Empty
Y00
Y02
Y04
Y06
Y08
Y0A
Y0C
Y0E
COM
100 to 240VAC
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18