APPENDICES
A
Appendix
 1 Det
ails of
 I
/O
 S
ignal
s
Appendix
 1.
1 I
nput
 signals
(6) CH Counter value large (point No.2) (X5, XC)
• This signal turns on when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is larger than CH 
Coincidence output point No.2 (Un\G6, Un\G7, Un\G38, Un\G39).
• This signal turns off when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is equal to or smaller than 
CH Coincidence output point No.2 (Un\G6, Un\G7, Un\G38, Un\G39).
(7) CH Counter value coincidence (point No.2) (X6, XD)
• This signal turns on when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is equal to CH 
Coincidence output point No.2 (Un\G6, Un\G7, Un\G38, Un\G39). And then, the on status will be latched.
• This signal is turned off by CH Coincidence signal No.2 reset command (Y07, YF).
• This signal is on immediately after the CPU module is powered on or is reset because both CH Present 
value (Un\G2, Un\G3, Un\G34, Un\G35) and CH Coincidence output point No.2 (Un\G6, Un\G7, Un\G38, 
Un\G39) are set to "0".
(8) CH Counter value small (point No.2) (X7, XE)
• This signal turns on when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is smaller than CH 
Coincidence output point No.2 (Un\G6, Un\G7, Un\G38, Un\G39).
• This signal turns off when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is equal to or larger than 
CH Coincidence output point No.2 (Un\G6, Un\G7, Un\G38, Un\G39).