For the 1-phase pulse input, check that for up count, the phase B pulse input and CH Down count command (Y3, YB) are 
off before performing the phase A pulse input.
If at least one of the B phase pulse input and CH Down count command (Y3, YB) is on, pulses are counted down in the A 
phase pulse input.
2-phase multiple of 2
At up count
Counts on the rising edge (
) of A while B is off.
Counts on the falling edge (
) of A while B is on.
At down count
Counts on the rising edge (
) of A while B is on.
Counts on the falling edge (
) of A while B is off.
2-phase multiple of 4
At up count
Counts on the rising edge (
) of A while B is off.
Counts on the falling edge (
) of A while B is on.
Counts on the rising edge (
) of B while A is on.
Counts on the falling edge (
) of B while A is off.
At down count
Counts on the rising edge (
) of A while B is on.
Counts on the falling edge (
) of A while B is off.
Counts on the rising edge (
) of B while A is off.
Counts on the falling edge (
) of B while A is on.
Pulse input mode
Count timing
A
B
A
B
A
B
A
B