Mitsubishi Electronics 0 ユーザーズマニュアル

ページ / 136
74
(2) Performing the preset function using an external control signal
Perform the preset function by applying an ON voltage to the preset input terminal for external input.
While CH External preset request detection (X4, XB) is on (3)), the preset function cannot be performed even if a voltage 
is applied to the preset input terminal or CH Preset command (Y1, Y9) is turned on.
The preset function can be performed when CH External preset request detection (X4, XB) is turned off by turning on CH 
External preset detection reset command (Y5, YD) (4)).
No.
Description
1)
Write a value to CH Preset value (Un\G0, Un\G1, Un\G32, Un\G33) in 32-bit signed binary.
2)
On the rising edge (off to on) of the preset command (A voltage is applied to the preset input terminal.), the value 
stored in CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is replaced with the value stored in CH Preset 
value (Un\G0, Un\G1, Un\G32, Un\G33).
The preset function is performed regardless of the on/off status of CH Count enable command (Y4, YC).
0
2)
4)
3)
1)
100
2)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
101
66
65
2
1
0
123 124 100 101
100
67
to
to
Counter input pulse
CH    Count enable command 
(Y4, YC)
CH    Preset value 
(Un\G0, Un\G1, Un\G32, Un\G33)
Preset command 
(preset input terminal)
CH    External preset 
request detection 
(X4, XB)
CH    External preset 
detection reset command 
(Y5, YD)
CH    Present value 
(Un\G2, Un\G3, Un\G34, Un\G35)