Mitsubishi Electronics Q68RD3-G ユーザーズマニュアル

ページ / 212
6
 - 21
6.3 Using Programs on Remote I/O Network
6.3.2 Program example when utility package is used
6
PROGRAMMING
6.3.2
Program example when utility package is used
(1) List of devices
Table 6.7 List of devices
Device
Function
W0
Device that Conversion completion flag is written by auto refresh
W1
Device that CH1 Measured temperature value is written by auto refresh
W2
Device that CH2 Measured temperature value is written by auto refresh
W3
Device that CH3 Measured temperature value is written by auto refresh
W4
Device that Error code is written by auto refresh
W5
Device that Warning output flag (Process alarm) is written by auto refresh
W6
Device that Warning output flag (Rate alarm) is written by auto refresh
W7
Device that Disconnection detection flag is written by auto refresh
D11
CH1 Measured temperature value
D12
CH2 Measured temperature value
D13
CH3 Measured temperature value
X20
Device that user turns ON to start reading 
measured temperature values
QX10 (X20 to X2F)
X21
Device that user turns ON to reset a 
disconnection detection state
X22
Device that user turns ON to reset an 
error
Y30 to Y3B
Error code display (BCD 3 digits)
QY10 (Y30 to Y3F)
X100
Module ready
Q68RD3-G (X/Y100 to X/Y10F)
X10C
Disconnection detection signal
X10F
Error flag
Y10F
Error clear request