Mitsubishi Electronics Q68RD3-G ユーザーズマニュアル

ページ / 212
7
 - 24
7.3 Procedures of Online Module Change
7.3.5 When user range setting is used and initial setting has been made with sequence program (Separate
7
ONLINE MODULE CHANGE
7.3.5
When user range setting is used and initial setting has been made 
with sequence program (Separate system is available)
(1) Disabling conversion
(a) Set the Conversion enable/disable setting (Un\G0) to "Disable" for all channels 
and turn Operating condition setting request (Y9) from OFF to ON to stop 
conversion.
After confirming that conversion has stopped with the Conversion completion flag 
(Un\G10), turn OFF Operating condition setting request (Y9).
(2) Removing a module
(a) On the screen displayed by selecting [Diagnosis] - [Online module change] in GX 
Developer, select the "Online module change" mode and double-click the module 
to be changed online to display the "Online module change" screen.