Mitsubishi Electronics Q68RD3-G ユーザーズマニュアル

ページ / 212
3
 - 4
3.2 Function List
3.2.1 Temperature conversion system
3
SPECIFICATIONS
3.2.1
Temperature conversion system
The following shows the temperature measurement timing within each conversion period.
Temperatures of all channels, CH1 to CH8, are batch-updated every 320ms, regardless of 
the Conversion enable/disable setting (Un\G0).
If the Conversion enable/disable setting (Un\G0) of a channel is set to "Enable" when the 
temperature is measured, the measured temperature value is stored in the CH  
Measured temperature value (Un\G11 to Un\G18). If the setting is set to "Disable", the 
measured temperature value is not stored.
Regardless of the number of conversion-enabled channels, the measured temperature 
values are stored in the buffer memory every 320ms.
The following shows the temperature measurement timing within each conversion period.
Conversion period (320ms)
Conversion period (320ms)
Conversion period (320ms)
Update timing
CH1 to CH8 
Measured 
temperature values 
batch-updated
Update timing
CH1 to CH8 
Measured 
temperature values 
batch-updated
Update timing
CH1 to CH8 
Measured 
temperature values 
batch-updated
Update timing
CH1 to CH8 
Measured 
temperature values 
batch-updated