Mitsubishi Electronics Q68RD3-G ユーザーズマニュアル

ページ / 212
5
UTILITY PACKAGE (GX Configurator-TI)
5.1 Utility Package Functions
5
 - 1
1
O
V
ER
VI
E
W
2
SY
STEM
 
CONFIGURA
TION
3
SP
ECIFICA
T
IONS
4
P
R
OC
EDU
R
ES
 A
ND 
SE
TTINGS B
E
FORE
 
SY
STEM
 O
PER
A
T
ION
5
UTIL
ITY P
A
CK
AGE
 
(GX CONFIGURA
T
O
R-TI)
6
P
R
OGRAM
M
ING
7
ONLINE MO
D
U
LE
 
CH
A
N
G
E
8
TR
O
U
B
L
E
S
HOOTING
CHAPTER5 UTILITY PACKAGE (GX Configurator-TI)
5.1
Utility Package Functions
Table 5.1 lists the utility package functions.
Table 5.1 List of utility package (GX Configurator-TI) functions (1/2)
Function
Description
Reference
Initial setting
(1)  Makes initial setting of the following items, which are required to operate the Q68RD3-G, for each 
channel.
•Conversion enable/disable setting
•Rate alarm warning detection period
•Averaging processing selection
•Rate alarm upper limit value
•Time/count/moving average/time constant setting
•Rate alarm lower limit value
•Process alarm warning output enable/disable setting
•Scaling range lower limit value
•Setting range
•Scaling range upper limit value
•Process alarm lower lower limit value
•Scaling valid/invalid setting
•Process alarm lower upper limit value
•Scaling width lower limit value
•Process alarm upper lower limit value
•Scaling width upper limit value
•Process alarm upper upper limit value
•Conversion setting for disconnection 
detection
•Rate alarm warning output enable/disable setting
•Conversion setting value for disconnection 
detection
(2)  The initial setting data are registered in the parameter of the programmable controller CPU and 
automatically written to the Q68RD3-G when the programmable controller CPU changes to the RUN 
status.
Auto refresh
setting
(1)  Sets the automatically refreshed Q68RD3-G buffer memory for each channel.
•Conversion completion flag
•Setting range (Offset/gain setting CH1-CH8)
•CH  Measured temperature value
•Warning output flag (Process alarm)
•Error code
•Warning output flag (Rate alarm)
•Setting range (Input type CH1-CH4)
•Disconnection detection flag
•Setting range (Input type CH5-CH8)
•CH  Scaling value
(2)  The values stored in the Q68RD3-G buffer memory where auto refresh setting has been made are 
automatically read from/written to the device when the END instruction of the programmable controller 
CPU is executed.