2 - 5 2 - 5
MELSEC-Q
2 SYSTEM CONFIGURATION
2.2.2 Setting items
(1) Table 2.3 lists the parameter setting items of the multiplexed remote master
station (DM
R
) and multiplexed remote sub-master station (DSM
R
).
Table 2.3 Setting Items of Multiplexed Remote Master Station and
Multiplexed Remote Sub-Master Station
Multiplexed Remote Sub-Master Station
Setting item
Multiplexed remote
master station (DM
R
)
Multiplexed remote
sub-master station
(DSM
R
)
Reference
Network module switch
STATION NO.
0
1 to 64
Section 4.2.1
MODE
Section 4.2.1
Parameter setting on GX Developer
Setting the number of Ethernet/CC IE/MELSECNET cards
Network type
MELSECNET/H
(Multiplexed remote
master station)
MELSECNET/H
(Multiplexed remote
sub-master station)
Section 5.1.1
Starting
I/O
Section 5.1.2
Network
No.
Section 5.1.2
Total
stations
1
Section 5.1.2
Group
No.
Section 5.1.2
Mode
Section 5.1.2
Common
parameters
1
Section 5.1.3
Supplementary
setting
Section 5.1.4
Station specific parameters
—
Refresh
parameters
2
3
2
3
Section 5.1.5
Valid module during other
station access
Section 5.1.6
Interlink transmission parameter
—
Routing
parameters
4
: Always set, : Default setting, : Set as needed, : No need to set
POINT
1: Set Total stations and common parameters of the multiplexed remote sub-
master station when using the multiplexed remote sub-master station to
resume the network. The settings must be the same as those of the
multiplexed remote master station.
resume the network. The settings must be the same as those of the
multiplexed remote master station.
For example, if the multiplexed remote master station is powered off and then
on during network control by the multiplexed remote sub-master station, the
multiplexed remote sub-master station resumes networking as a master
operating station.
on during network control by the multiplexed remote sub-master station, the
multiplexed remote sub-master station resumes networking as a master
operating station.
2 : Default values are not set in LX/LY. Set the refresh parameters.
3 : Default values are preset for LB/LW.
3 : Default values are preset for LB/LW.
The system may operate even if refresh parameters have not been set.
For the operation and precautions, refer to Section 5.1.5 (3).
For the operation and precautions, refer to Section 5.1.5 (3).
4 : Refer to the Q Corresponding MELSECNET/H Network System Reference
Manual (PLC to PLC Network) (SH-080049).