2   SYSTEM CONFIGURATION 
 
2.6 When Using a Multiple CPU System 
Take the following points into consideration when configuring a remote I/O network by 
utilizing multiple CPU system. 
 
(1)  Use the master module of function version B or later. 
 
(2)  Set the network parameters to the control CPU controlling the master module. 
 
(3)  It is possible to set up to four master modules per control CPU. Note that the 
maximum number of mountable master modules per multiple CPU system is four. 
 
(a)  CPU No. 1 controls all master modules 
(b)  CPU No. 1 and CPU No. 2 control each master 
module 
 
QJ71
BR11
QJ71
BR11
QJ71
BR11
QJ71
BR11
CPU
No. 1
CPU
No. 2
 
 
QJ71
BR11
QJ71
BR11
QJ71
BR11
QJ71
BR11
CPU
No. 1
CPU
No. 2
 
 
(c)  CPU No 1 to No. 4 control each master module 
(d)  The maximum number of mountable master 
modules per system is four 
 
CPU
No. 2
CPU
No. 1
QJ71
BR11
QJ71
BR11
QJ71
BR11
QJ71
BR11
CPU
No. 3
CPU
No. 4
 
 
QJ71
BR11
QJ71
BR11
QJ71
BR11
QJ71
BR11
QJ71
BR11
CPU
No. 1
CPU
No. 2
: The number of mounted modules exceeds the limit by one.