2 - 8                                                                                                                                                             2 - 8 
MELSEC-Q
2   SYSTEM CONFIGURATION 
 
2.3.2 Setting items 
(1)  Table 2.5 lists the parameter setting items of the multiplexed remote master 
station (DM
R
) and multiplexed remote sub-master station (DSM
R
). 
In the redundant system, the same network parameters are set to both the 
control and standby systems. For this reason, parameter setting for the 
multiplexed remote sub-master station is not required. 
Make sure to assign No.0 to the master module mounted on the system A CPU 
in the redundant system. 
 
Table 2.5 Setting Items of a Multiplexed Remote Master Station and 
a Multiplexed Remote Sub-master Station 
Setting items 
Remote master 
station (M
R
Remote sub-
master station 
(DSM
R
Reference 
Tracking cable connector 
System A 
System B 
Section 7.1.1 
Network module switch 
 
STATION NO. 
1 to 64 
Section 4.2.1 
 MODE 
 
 
Section 4.2.1 
Parameter setting on GX Developer 
 
Setting the number of Ethernet/CC IE/MELSECNET cards 
 
 
Network type 
MELSECNET/H
(Remote master 
station) 
 
Section 5.1.1 
 
 
Starting I/O No. 
 
 
Section 5.1.2 
 
 
Network No. 
 
 
Section 5.1.2 
 
 
Total stations 
 
 
Section 5.1.2 
 
 
Group No. 
 
— 
 
 
Mode 
 
 
Section 5.1.2 
 
Common parameters 
 
 
Section 5.1.3 
 
Supplementary setting 
 
 
Section 5.1.4 
 
Station specific parameters 
 
— 
 
Refresh parameters 
1
2
 
 
Section 5.1.5 
 
Valid module during other station access 
 
 
Section 5.1.6 
 
Interlink data transfer parameters 
 
— 
 
Setting of redundant configuration 
 
 
Section 5.1.7 
 
Routing parameters 
 
 
: Always set,  : Default setting,  : Set as needed,  : No need to set 
 
1: Default values are not set in LX/LY. Set the refresh parameters. 
2: Default values are preset for LB/LW. 
The system may operate even if refresh parameters have not been set. 
For the operation and precautions, refer to Section 5.1.5 (3). 
3: Refer to the Q Corresponding MELSECNET/H Network System Reference 
Manual (PLC to PLC Network) (SH-080049).