Mitsumi electronic IB-1500875(ENG)-E ユーザーズマニュアル

ページ / 352
6 Specifications of Peripheral Devices
MITSUBISHI CNC
6 - 8
6-2 Selection of circuit protector and contactor
Always select the circuit protector and contactor properly, and install them to each power supply unit to prevent 
disasters.
6-2-1 Selection of circuit protector
Calculate a circuit protector selection current from the rated output and the nominal input voltage (voltage 
supplied to the power supply unit) as in the expression below. And then select the minimum capacity circuit 
protector whose rated current meets the circuit protector selection current.
< MDS-D Series >
Circuit protector selection current [A] = 
(Circuit protector selection current for 200V input [A] / Nominal input voltage [V]) × 200 [V]
Selection of circuit protector for 200V input
Option part: A circuit protector is not prepared as an NC unit accessory, so purchase the part from your 
dealer, etc.
< MDS-DH Series >
Circuit protector selection current [A] = 
(Circuit protector selection current for 380V input [A] / Nominal input voltage [V]) × 380 [V]
Selection of circuit protector for 380V input
Option part: A circuit protector is not prepared as an NC unit accessory, so purchase the part from your 
dealer, etc.
Unit type
MDS-D-CV-
37
75
110
185
300
370
450
550
Rated output
3.7kW
7.5kW
11kW
18.5kW
30kW
37kW
45kW
55kW
Circuit protector selection 
current for 200V input
15A
31A
45A
76A
124A
153A
186A
224A
Selection example of circuit protector
(Mitsubishi Electric Corp.)
NF63-
CW3P-
20A
NF63-
CW3P-
40A
NF63-
CW3P-
50A
NF125-
CW3P-
100A
NF250-
CW3P-
125A
NF250-
CW3P-
175A
NF250-
CW3P-
200A
NF250-
CW3P-
225A
Rated current of the selection example
of circuit protector
20A
40A
50A
100A
125A
175A
200A
225A
(Example)
Select a circuit protector for using the MDS-D-CV-110 with a 220V nominal input voltage.
Circuit protector selection current = 45/220 × 200 = 40.9[A]
According to the table above, select "NF63-CW3P-50A".
Unit type
MDS-DH-CV-
37
75
110
185
300
370
450
550
750
Rated output
3.7kW
7.5kW
11kW
18.5kW
30kW
37kW
45kW
55kW
75kW
Circuit protector selection current for 
380V input
8A
16A
24A
40A
65A
80A
98A
119A
163A
Selection example of circuit protector
(Mitsubishi Electric Corp.)
NF63-
CW3P-
10A
NF63-
CW3P-
20A
NF63-
CW3P-
30A
NF63-
CW3P-
40A
NF125-
CW3P-
75A
NF125-
CW3P-
100A
NF125-
CW3P-
100A
NF250-
CW3P-
125A
NF250-
CW3P-
200A
Rated current of the selection example
of circuit protector
10A
20A
30A
40A
75A
100A
100A
125A
200A
(Example)
Select a circuit protector for using the MDS-DH-CV-450 with a 480V nominal input voltage.
Circuit protector selection current = 98/480×380 = 77.6[A]
According to the table above, select "NF125-CW3P-100A".
1. It is dangerous to share a circuit protector for multiple power supply units, so do not share it. 
Always install the circuit protectors for each power supply unit.
2. If the control power (L11, L21) must be protected, select according to the section "6-4-1 Circuit 
protector ".
CAUTION