Mitsubishi Electronics MR-MC241 ユーザーズマニュアル
7 - 40
7. AUXILIARY FUNCTION
7.12.2 Command/status bit
System command/status bits related to sampling function are shown below.
System command
System status
Address Bit Symbol
Signal
name
Address
Bit Symbol
Signal
name
03E1 0 SMPS
Sampling
start
0451
0
SMPW
Waiting for sampling trigger
1
Reserved
1
SMPO
Sampling is being performed
2
2 SMPF
Sampling
is
complete
3
3 SMPE
Sampling
error
4
4
Reserved
5
5
6
6
7
7
Address Bit Symbol
Signal
name
Address
Bit Symbol
Signal
name
03F2
0 SMPSW
Sampling setting write
command
command
0462
0 SWFIN
Sampling setting write
complete
complete
1
Reserved
1 SWEN
Sampling setting number error
2
2 SWED
Sampling setting data out of
bounds
bounds
3
3
Reserved
4 SMPSR
Sampling setting read
command
command
4 SRFIN
Sampling setting read
complete
complete
5
Reserved
5 SREN
Sampling setting number error
6
6
Reserved
7
7
(1) Details concerning system command bits
Symbol Signal
name
Function
details
SMPS Sampling
start
[Function]
Starts sampling.
[Operation]
When the sampling start signal (SMPS) is turned on, storage of sampling data is started.
SMPSR Sampling
setting
read command
[Function]
Reads sampling setting.
[Operation]
Reads sampling setting set to sampling setting read number. When the sampling setting read
number is incorrect, sampling setting read will not be performed.
(Remarks) The sampling setting read command is valid only while system is running.
number is incorrect, sampling setting read will not be performed.
(Remarks) The sampling setting read command is valid only while system is running.
SMPSW Sampling
setting
write command
[Function]
Writes sampling setting.
[Operation]
Writes sampling setting set to sampling setting write number. When the sampling setting
write number is incorrect and the sampling setting to be written is outside the setting range,
the sampling setting write will not be performed.
(Remarks) The sampling setting write command is valid only while system is running.
write number is incorrect and the sampling setting to be written is outside the setting range,
the sampling setting write will not be performed.
(Remarks) The sampling setting write command is valid only while system is running.