Electrical Requirements
M414905
46
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
75 Pound Gas and Steam Models
NOTE: Wire size and breaker ratings were 
obtained from the Canadian Electrical Code for 
75 C. wire and are intended for use as a guideline 
only. Electrical connections should be made by a 
qualified electrical contractor in accordance with 
all applicable local and national requirements.
NOTE: Electrical specifications below are subject 
to change without notice. Always refer to product 
serial plate for most current specifications of 
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of “single 
phasing” and causing premature failure of the 
motor(s).
Serial Plate Rating
Terminal Block 
Connections 
Required
Serial Plate Amps
Recommended Circuit
Nonreversing
Reversing
Breaker 
Rating
Wire Size
AWG (mm
2
)
120V/60Hz/1ph
L1, Neutral and ground
13.8
N/A
20A – 1 pole
12 (3.31)
200-208V/60Hz/1ph
L1, Neutral and ground
7.6
N/A
15A – 1 pole
14 (2.08)
200-208-240V/60Hz/
1ph
L1, L2 and ground
7.6
N/A
15A – 2 pole
14 (2.08)
230-240V/50Hz/1ph
L1, Neutral and ground
6.7
7.0
15A – 1 pole
14 (2.08)
200-208V/60Hz/3ph
L1, L2, L3 and ground
3.8
4.3
10A – 3 pole
14 (2.08)
200V/50Hz/3ph
L1, L2, L3 and ground
3.5
4.5
10A – 3 pole
14 (2.08)
240V/60Hz/3ph
L1, L2, L3 and ground
3.8
4.3
10A – 3 pole
14 (2.08)
230-240V/50Hz/3ph
L1, L2, L3 and ground
3.5
4.9
10A – 3 pole
14 (2.08)
380V/50 or 60Hz/3ph
L1, L2, L3 and ground
1.8
2.1
10A – 3 pole
14 (2.08)
400-415V/50Hz/3ph
L1, L2, L3 and ground
1.8
2.1
10A – 3 pole
14 (2.08)
440V/60Hz/3ph
L1, L2, L3 and ground
1.9
2.1
10A – 3 pole
14 (2.08)
460-480V/60Hz/3ph
L1, L2, L3 and ground
1.9
2.1
10A – 3 pole
14 (2.08)
N/A = Not Applicable
Table 8 
F75 Gas Models Only
Serial Plate Rating
Terminal Block 
Connections 
Required
Serial Plate Amps
Recommended Circuit
Nonreversing
Reversing
Breaker 
Rating
Wire Size
AWG (mm
2
)
200-208V/60Hz/3ph
L1, L2, L3 and ground
N/A
6.3
15A – 3 pole
14 (2.08)
240V/60Hz/3ph
L1, L2, L3 and ground
N/A
6.3
15A – 3 pole
14 (2.08)
460-480V/60Hz/3ph
L1, L2, L3 and ground
N/A
3.1
10A – 3 pole
14 (2.08)
N/A = Not Applicable
Table 9