KitchenAid FRONT-LOADING GAS DRYER ユーザーズマニュアル

ページ / 44
11
Determine vent path
Select the route that will provide the straightest and most 
direct path outdoors. 
Plan the installation to use the fewest number of elbows and 
turns. 
When using elbows or making turns, allow as much room as 
possible. 
Bend vent gradually to avoid kinking. 
Use the fewest 90° turns possible.
Determine vent length and elbows needed for best 
drying performance
Use one of the following Vent system charts to determine 
type of vent material and hood combinations acceptable to 
use.
NOTE: Do not use vent runs longer than those specified in 
the Vent system charts. Exhaust systems longer than those 
specified will:
Shorten the life of the dryer.
Reduce performance, resulting in longer drying times and 
increased energy usage.
The Vent system charts provide venting requirements that will 
help to achieve the best drying performance.
Vent system chart 1 - rigid metal vent only
Vent system chart 2 - rigid metal vent used with a 
maximum of 8 ft (2.4 m) flexible metal vent
Install Vent System
1. Position the dryer so that the rear of the dryer is within 4 ft 
(1.2 m) of its final location.
2. Install exhaust hood. Use caulking compound to seal exterior 
wall opening around exhaust hood.
3. Connect vent to exhaust hood. Vent must fit inside exhaust 
hood. Secure vent to exhaust hood with 4" (10.2 cm) clamp.
4. Run vent to dryer location. Use the straightest path possible. 
See “Determine vent path” in “Plan Vent System.” Avoid 90º 
turns. Use clamps to seal all joints. Do not use duct tape, 
screws or other fastening devices that extend into the interior 
of the vent to secure vent.
Make Gas Connection
1. Remove the blue cap from the gas pipe. Move the dryer close 
to its final location.
2. Using a wrench to tighten, connect the gas supply to the 
dryer. Use pipe-joint compound on all non-flared male 
threads. If flexible metal tubing is used, be sure there are no 
kinks.
NOTE: For LP gas connections, you must use pipe-joint 
compound resistant to the action of LP gas. Do not use 
TEFLON
®† 
tape.
A combination of pipe fittings must be used to connect the 
dryer to the existing gas line. Shown following is a 
recommended connection. Your connection may be different, 
according to the supply line type, size and location.
3. Open the shutoff valve in the supply line. The valve is open 
when the handle is parallel to the gas pipe.
4. Test all connections by brushing on an approved 
noncorrosive leak-detection solution. Bubbles will show a 
leak. Correct any leak found.
Number of 
90º turns 
or elbows
Type of
vent
Box or 
louvered 
hoods
Angled
hoods
0
Rigid metal
174 ft (53.0 m)
168 ft (51.2 m)
1
Rigid metal
164 ft (50.0 m)
158 ft (48.0 m)
2
Rigid metal
154 ft (46.9 m)
148 ft (45.1 m)
3
Rigid metal
145 ft (44.2 m)
139 ft (42.4 m)
4
Rigid metal
137 ft (41.8 m)
131 ft (39.9 m)
Number of 
90º turns 
or elbows
Type of
vent
Box or 
louvered 
hoods
Angled
hoods
0
Rigid metal
144 ft (43.9 m)
138 ft (42.1 m)
1
Rigid metal
134 ft (40.8 m)
128 ft (39.0 m)
2
Rigid metal
125 ft (38.1 m)
119 ft (36.3 m)
3
Rigid metal
117 ft (35.7 m)
111 ft (33.8 m)
A.
³⁄₈
" flexible gas connector
B.
³⁄₈
" dryer pipe
C.
³⁄₈
" to 
³⁄₈
" street el
D.
³⁄₈
" pipe-to-flare adapter fitting
A. Closed valve
B. Open valve
WARNING
Excessive Weight Hazard
Use two or more people to move and install dryer.
Failure to do so can result in back or other injury.
†®TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
A
B
C
D
A