Installation Requirements
       WARNING
FIRE HAZARD
Exceeding the length of duct pipe or number
of elbows allowed in the “MAXIMUM LENGTH”
charts can cause an accumulation of lint in the 
exhaust system. Plugging the system could
create a fire hazard, as well as increase drying 
times.
       WARNING
FIRE HAZARD
A clothes dryer must be exhausted outdoors.
Do not exhaust dryer into a chimney, a wall, a
ceiling, an attic, a crawl space or any concealed 
space of a building.  A clothes dryer produces 
combustible lint. If the dryer is not exhausted
outdoors, some fine lint will be expelled into the
laundry area. An accumulation of lint in any area 
of the home can create a health and fire hazard.
The dryer must be connected to an exhaust
outdoors. Regularly inspect the outdoor exhaust
opening and remove any accumulation of lint 
around the outdoor exhaust opening and in the
surrounding area.
Install male fittings in correct direction:
In installations where the exhaust system is not
described in the charts, the following method 
must be used to determine if the exhaust system
is acceptable:
Exhaust system requirements, continued
Number of 90°  tur
ns
MAXIMUM LENGTH
of 4” (10.2cm) Rigid Metal Duct
VENT HOOD TYPE
(Preferred)
4”
(10.2cm)
louvered
2.5”
(6.35cm)
0
125 ft. (38.10m)
110 ft. (33.53m)
1
115 ft. (35.05m)
100 ft. (30.48m)
2
105 ft. (32.00m)
90 ft. (27.43m)
3
95 ft. (28.96m)
80 ft. (24.38m)
4
85 ft. (25.91m)
70 ft. (21.34m)
Number of 90°  tur
ns
MAXIMUM LENGTH
of 4” (10.2cm) Semi-Rigid Metal Duct
VENT HOOD TYPE
(Preferred)
4”
(10.2cm)
louvered
2.5”
(6.35cm)
0
60 ft. (18.29m)
45 ft. (13.72m)
1
50 ft. (15.24m)
35 ft. (10.67m)
2
40 ft. (12.19m)
25 ft. (7.62m)
3
NOT RECOMMENDED
CORRECT
INCORRECT
       WARNING
FIRE HAZARD
Do not allow combustible materials (for
example: clothing, draperies/curtains, paper)
to come in contact with exhaust system. The
dryer MUST NOT be exhausted into a chimney,
a wall, a ceiling, or any concealed space of a 
building which can accumulate lint, resulting in 
a fire hazard.
Do not screen the exhaust ends of the vent
system, or use any screws, rivets or other 
fasteners that extend into the duct to assemble
the exhaust system. Lint can become caught
in the screen, on the screws or rivets, clogging 
the duct work and creating a fire hazard as well 
as increasing drying times. Use an approved 
vent hood to terminate the duct outdoors, and 
seal all joints with duct tape. All male duct pipe
fittings MUST be installed downstream with the
flow of air.