1   OVERVIEW 
 
1.5 System Settings 
1.5.1 System data settings 
The table below lists the system data items to be set. 
 
 
Item 
Setting range 
Initial value 
Remark 
CPU base 
2/3/5/8/10/12 slots 
CPU base : 2 slots 
Base setting 
Extension base 
None/2/3/5/8/10/12 slots 
None 
Set the number of slots in the CPU base 
or extension base. 
Number of Multiple 
CPUs 
2/3/4 modules 
2 modules 
Set the total number of Multiple CPUs 
including PLC CPU(s). 
Automatic refresh 
setting 
Up to 2k words of devices 
(D/W/#/M/Y/B) can be set per 
CPU for settings 1 to 4. 
None 
Set the automatic refresh between CPUs 
using Multiple CPU shared memory. 
Multiple CPU 
setting 
Error operation mode 
at the stop of CPU 
Stop/do not stop all CPUs 
upon an error in CPU Nos. 
1/2/3/4. 
(The setting range varies 
depending on the number of 
Multiple CPUs installed.) 
Stop all CPUs upon 
error in CPU Nos. 
1/2/3/4 
Set whether or not to stop the entire 
system when a CPU stop error occurs in 
each CPU. 
Module arrangement 
Within the CPU base and 
extension base slots 
None 
Install the modules controlled by the self 
CPU in the CPU base and/or extension 
base(s). 
Common 
system 
parameters 
Motion slot 
setting 
Individual module 
Varies depending on the 
module. 
Varies depending on 
the module. 
Set detailed items for each module 
controlled by the self CPU. 
Operation cycle setting 
0.8 ms/1.7 ms/3.5 ms/7.1 
ms/14.2ms/Auto 
Auto 
Set the operation cycle of motion control. 
Operation at STOP to 
RUN 
M2000 is turned on with switch 
(STOP to RUN). M2000 
becomes a switch set (STOP 
to RUN) + register by single-
unit with turning on. 
M2000 is turned on 
with switch (STOP to 
RUN). 
Set the condition in which the PLC ready 
flag (M2000) turns on. 
Forced stop 
(Note)
 
None/X (PX) (0 to 1FFF)/ 
M (0 to 8191) 
None 
Set the bit device used for forced stop. 
Basic system 
setting 
Latch range 
M (0 to 8191)/B (0 to 1FFF)/F 
(0 to 2047)/D (0 to 8191)/W (0 
to 1FFF) 
None 
Set the latch range of device memory. 
Self CPU installation position setting 
Set self CPU/another 
CPU/CPU (empty) for slots 
0/1/2. (The setting range 
varies depending on the 
number of Multiple CPUs 
installed.) 
None 
(When two CPUs are 
installed, slot 0 is 
fixed as the self 
CPU.) 
Set the installation position of the self 
CPU in the CPU base. 
Servo amplifier/motor setting 
Q173CPU(N): 
 Up to 2 systems, 32 axes 
Q172CPU(N): 
 Up to 1 system, 8 axes 
None 
Set the model name, axis No. and other 
details for the servo amplifiers and 
servomotors. 
High-speed read setting 
One Q172EX/Q173PX module 
and one input module. 
None 
Set the high-speed read data.  
Refer to "Q173CPU(N)/Q172CPU(N) 
Motion controller (SV13/SV22) 
Programming Manual (Real Mode)" for 
the high-speed read function. 
Individual 
parameters 
Battery setting 
External battery unused/ 
External battery used 
External battery 
unused. 
Set whether or not to use an external 
battery. If the power supply is down for 
one month or longer, data must be 
backed up with an external battery.  
Refer to "Q173CPU(N)/Q172CPU(N) 
User’s Manual" for external battery. 
(Note) : The forced stop can also be executed by the forced stop terminal of the servo amplifier besides the forced stop input setting.