4   AUXILIARY AND APPLIED FUNCTIONS 
 
4.11 Connect/Disconnect Function 
This function is used to temporarily suspend SSCNET communication while servo 
amplifiers and/or SSCNET  cables after Axis 1 are exchanged with the power supply 
ON in a Multiple CPU system.  
SD803 is required for connect/disconnect and SD508 stores the command status for 
"accept waiting" or "execute waiting" during this process. If a servo amplifier was 
previously removed using the connect/disconnect function, it must be used again to 
reconnect the servo amplifier. This function is only required when there is a desire to 
maintain communication to all axes in front of the one being removed. 
No connect/disconnect processing is required if the power supply to Axis 1 is 
shutdown. 
 
(1) Connect/disconnect status devices 
 
Device No. 
Overview 
Set by 
The execute status for a connect/disconnect is stored. 
  
 Monitoring 
value 
Status 
Contents 
 
 0 
Connect/disconnect 
command accept waiting 
Connect command or disconnect command is in the status 
that can be accepted  
 
 -1 
Connect/disconnect 
execute waiting 
SD508 is waiting for connect/disconnect execute command 
after accepting a connect command or disconnect command. 
 
 -2 
While 
connecting/disconnecting
Connect/disconnect is in process.  
 
SD508 
   
 
 
 
System 
 
(2) Connect/disconnect command devices 
 
Device No. 
Overview 
Set by 
The connect/disconnect command is set. 
 
 Setting 
value 
Command 
Contents 
 
 
None 
This value is set if there is no command. 
 
 
1 to 32 
Disconnect command 
Set axis No. "1 to 32" to be disconnected. 
 
 
-10 
Connect command 
Set to connect axis while disconnecting. 
 
 -2 
Connect/disconnect 
execute command 
Connect/disconnect processing is executed by setting this 
value in the status of a connect/disconnect execute waiting.  
 
SD803 
   
 
 
 
User