Mitsubishi Electronics QD77MS16 ユーザーズマニュアル
7 - 5
Chapter 7 Memory Configuration and Data Process
7.1.2 Buffer memory area configuration
The buffer memory of Simple Motion module is configured of the following types of
areas.
areas.
Buffer memory area configuration
Buffer memory address
Writing
possibility
QD77MS2/QD77MS4 QD77MS16
Parameter area
Basic parameter area
0+150n to 15+150n
Possible
Detailed parameter area
17+150n to 69+150n
OPR basic parameter area
70+150n to 78+150n
OPR detailed parameter area
79+150n to 91+150n
Expansion parameter area
100+150n to 149+150n
Mark detection setting parameter
area
area
54000+20k to 54019+20k
Monitor data area
System monitor area
1200 to 1499
31300 to 31549
4000 to 4299
31300 to 31549
Not possible
Axis monitor area
800+100n to 899+100n
2400+100n to 2499+100n
Mark detection monitor data area
54960+80k to 55039+80k
Control data area
System control data area
1900 to 1999
5900 to 5999
Possible
Axis control data area
1500+100n to 1599+100n
4300+100n to 4399+100n
Expansion axis control data area
30100+10n to 30109+10n
Mark detection control data area
54640+10k to 54649+10k
Positioning data area
(No.1 to 100)
(No.1 to 100)
Positioning data area
2000+6000n to 2999+6000n
6000+1000n to 6999+1000n
Positioning data area
(No.101 to 600)
(No.101 to 600)
3000+6000n to 7999+6000n
Set with GX Works2
Block start data area
(No.7000)
(No.7000)
Block start data area
26000+1000n to 26049+1000n
22000+400n to 22049+400n
26050+1000n to 26099+1000n
22050+400n to 22099+400n
Condition data area
26100+1000n to 26199+1000n
22100+400n to 22199+400n
Block start data area
(No.7001)
(No.7001)
Block start data area
26200+1000n to 26249+1000n
22200+400n to 22249+400n
26250+1000n to 26299+1000n
22250+400n to 22299+400n
Condition data area
26300+1000n to 26399+1000n
22300+400n to 22399+400n
Block start data area
(No.7002)
(No.7002)
Block start data area
26400+1000n to 26449+1000n
Set with GX Works2
26450+1000n to 26499+1000n
Condition data area
26500+1000n to 26599+1000n
Block start data area
(No.7003)
(No.7003)
Block start data area
26600+1000n to 26649+1000n
26650+1000n to 26699+1000n
26650+1000n to 26699+1000n
Condition data area
26700+1000n to 26799+1000n
Block start data area
(No.7004)
(No.7004)
Block start data area
26800+1000n to 26849+1000n
26850+1000n to 26899+1000n
26850+1000n to 26899+1000n
Condition data area
26900+1000n to 26999+1000n
PLC CPU memo area PLC CPU memo area
30000 to 30099