Mitsubishi Electronics QD77MS16 ユーザーズマニュアル

ページ / 1038
 
 
12 - 7 
Chapter 12    Expansion Control
 
12.1.4 Operation of speed-torque control 
[1]    Switching of control mode (Speed control/Torque control) 
 
  Switching method of control mode 
 
To switch the control mode to the speed control or the torque control, set "1" in 
"[Cd.138] Control mode switching request" after setting the control mode in 
"[Cd.139] Control mode setting". 
When the mode is switched to the speed control mode or the torque control mode, 
the control data used in each control mode must be set before setting "1" in 
"[Cd.138] Control mode switching request". 
When the switching condition is satisfied at control mode switching request, "30: 
Control mode switch" is set in "[Md.26] Axis operation status", and the BUSY 
signal turns ON. "0" is automatically stored in "[Cd.138] Control mode switching 
request" by Simple Motion module after completion of switching.   
A warning "Control mode switching during BUSY" (warning code: 120) or "Control 
mode switching during zero speed OFF" (warning code: 121) occurs if the 
switching condition is not satisfied, and the control mode is not switched. 
The following shows the switching condition of each control mode. 
 
Position control mode
Speed control mode
Torque control mode
3)
4)
2)
1)
5)
6)
 
 
Switching operation 
Switching condition 
1) Position 
control 
mode    Speed control mode 
Not during positioning 
(Note-1)
 and during motor 
stop 
(Note-2)
, (Note-3)
 
2)  Speed control mode 
  Position control mode 
During motor stop 
(Note-2)
, (Note-3)
 
3) Position 
control 
mode    Torque control mode
Not during positioning 
(Note-1)
 and during motor 
stop 
(Note-2), (Note-3)
 
4)  Torque control mode 
 Position control mode
During motor stop 
(Note-2), (Note-3)
 
5)  Speed control mode 
  Torque control mode 
None 
6)  Torque control mode 
  Speed control mode 
 
(Note-1): BUSY signal is OFF. 
(Note-2): ZERO speed (Low-order buffer memory address: b3 of "[Md.108] Servo status") is ON. 
 
 
Buffer memory address (Low-order) 
QD77MS2/QD77MS4
QD77MS16 
[Md.108] Servo status: b3 
876+100n 
2476+100n 
n: Axis No.-1 
 
(Note-3): The control mode can be changed without checking the switching condition of "during motor 
stop" in Simple Motion module by setting "1: Zero speed ON condition invalid (for switching 
control mode)" in "Condition selection at mode switching (b12 to b15)" of "[Pr.90] Operation 
setting for speed-torque control mode". Set "1: Zero speed ON condition invalid (for switching 
control mode)" only when switching the control mode without waiting for the servomotor to stop.