3   DESIGN 
 
3.2.1 Power supply circuit design 
This section describes the protective coordination and noise suppression techniques of 
the power supply circuit. 
(1)   Separation and protective coordination (leakage current protection, 
over current protection) of power supply systems 
When wiring, separate the lines of Multiple CPU system power supplies from 
those of the I/O equipment and servo amplifier as shown below. 
When there is much noise, connect an insulation transformer. 
 
Multiple CPU
system
PLC power
supply
Main power
supply
I/O power
supply
Main circuit
power supply
I/O devices
Main circuit device
Insulation
transformer
100/200VAC
T1
NFB
CP
CP
CP
200VAC
NFB
Servo amplifier
Servo amplifier
power supply
 
 
(2)   Grounding 
The Motion system may malfunction as it is affected by various noises such as 
electric path noises from the power supply systems, radiated and induced noises 
from other equipment, servo amplifiers and their cables, and electromagnetic 
noises from conductors. To avoid such troubles, connect the earthing ground of 
each equipment and the shield grounds of the shielded cables to the earth. 
Also use ferrite cores (ex., ZCAT3035-1330(TDK make)) to prevent the sneak 
noises from the SSCNET. 
For grounding, use the exclusive ground terminal wire of each equipment or a 
single-point earth method to avoid grounding by common wiring, where 
possible, since noises may sneak from other equipment due to common 
impedances. 
Multiple CPU
system 
Servo amplifier
Servo-
motor
Line noise filter
SSCNET
Ferrite cores
Panel personal 
computer
100/200VAC
 
(Note): Be sure to ground the line noise filter, Multiple CPU system, servo 
amplifier and servomotor. (Ground resistance : 100   or less)