Mitsubishi Electronics Q172CPU9(N) ユーザーズマニュアル

ページ / 234
 
 
 
3 - 15 
3   DESIGN 
 
3.3 Layout Design within The Control Panel 
3.3.1 Installation environment 
Install the Motion controller system in the following environment conditions. 
(1)   Ambient temperature is within the range of following conditions. 
 
Q173CPU/Q172CPU 
Number of 
the Motion CPU 
Q173CPUN(-T)/ 
Q172CPUN(-T) 
With Cooling fan unit 
(Shipped from the factory) 
Without Cooling fan unit 
0 to 40
°C (32 to 104°F) 
2 or more 
0 to 55
°C (32 to 131 °F) 
            —  
(Note-1)
 
(Note-1) : It is need to install the Cooling fan unit(Q170FAN). 
 
(2)   Ambient humidity is within the range of 5 to 95[%] RH. 
 
(3)   No condensing from sudden temperature changes 
 
(4)   No corrosive or inflammable gas 
 
(5)   There must not be a lot of conductible dust, iron filings, oil mist, or salt, organic  
solvents. 
 
(6)   No direct sunlight 
 
(7)  No strong electrical or magnetic fields 
 
(8)   No direct vibrations or shocks on the Motion controller