4   INSTALLATION AND WIRING 
 
4.5 Wiring 
4.5.1 Instructions for wiring 
 
!
 DANGER 
 Completely turn off the all lines of the power supply externally before wiring. Not completely turning off 
all power could result in electric shock or damage to the product. 
 When turning on the power supply or operating the module after wiring, be sure that the module's 
terminal covers are correctly attached. Not attaching the terminal cover could result in electric 
shock. 
 
!
 CAUTION 
 Be sure to ground of the earth terminal FG and LG. Not doing so could result in electric shock or 
operation failure. (Ground resistance: 100  or less) 
 When wiring in the Motion controller, be sure that it is done correctly by checking the product's rated 
voltage and the terminal layout. Connecting a power supply that is different from the rating or 
incorrectly wiring the product could result in fire or damage. 
 External connections shall be crimped or pressure welded with the specified tools, or correctly 
soldered. Imperfect connections could result in short circuit, fire, or operation failure. 
 Tighten the terminal screws within the specified torque range. If the terminal screws are loose, it could result in 
short circuit, fire, or operation failure. Tightening the terminal screws too far may cause damages to the screws 
and/or the module, resulting in drop, short circuit, or operation failure. 
 Be sure there are no foreign matters such as sawdust or wiring debris inside the module. Such debris 
could cause fire, damage, or operation
 failure. 
 The module has an ingress prevention label on its top to prevent foreign matter, such as wiring 
debris, from entering the module during wiring. 
Do not remove this label during wiring. 
Before starting system operation, be sure to remove this label because of heat dissipation. 
 
This section described instructions for the wiring of the power supply. 
 
(1)   Power supply wiring 
(a)   100VAC, 200VAC and 24VDC wires should be twisted as dense as possible 
respectively. Connect the modules with the shortest distance.
 
Also, to reduce the voltage drop to the minimum, use the thickest wires 
possible. 
Use the wires of the following core size for wiring. 
 
Application 
Recommended core size 
100VAC, 200VAC, 24VDC wires 
2.0mm
or less 
I/O equipment 
0.75mm
2
(0.75 to 1.5mm
2
 usable) 
Ground wire 
2.0mm
2
 or more