Mitsubishi Electronics Q172CPU9(N) ユーザーズマニュアル

ページ / 234
 
 
 
6 - 4 
6   INSPECTION AND MAINTENANCE 
 
6.2 Daily Inspection 
The items that must be inspected daily are listed below. 
 
Table 6.1 Daily Inspection 
Item Inspection 
item 
Inspection 
Criterion 
Action 
Installation of the base 
unit 
Check that the fixing 
screws are not loose and 
the cover is not dislocated. 
The screws and cover must be installed 
correctly. 
Retighten the 
screws. 
Installation of the I/O 
module, etc. 
Check that the module is 
not dislocated and the unit 
fixing hook is engaged 
correctly. 
The unit fixing hook must be engaged and 
installed correctly. 
Correctly 
engaged the 
unit fixing hook.
Check that terminal screws 
are not loose. 
Screws should not be loose. 
Retighten the 
terminal screws.
Check distance between of 
crimping terminals. 
Crimping terminals must be positioned at 
proper intervals. 
Correct. 
3 Connecting 
condition 
Check connectors of 
extension cable. 
Connector must not be loose. 
Retighten the 
connector fixing 
screws. 
P
ower s
uppl
y m
odul
Power supply 
[POWER] LED 
Check that the LED is ON. 
The LED must be ON (green). 
 (Abnormal if the LED is OFF.) 
CPU 
[RUN] LED 
Check that the LED is ON 
in RUN state. 
The LED must be ON. 
 (Abnormal if the LED is OFF.) 
CPU 
[ERR.] LED 
Check that the LED is OFF.
The LED must be OFF. 
 (Abnormal if the LED is ON or flickers.) 
CPU 
[USER] LED 
Check that the LED is ON. 
The LED must be ON in the detection of CHK 
instruction or annunciator [F] is ON. 
CPU 
[BOOT] LED 
Check that the LED is 
ON/OFF. 
The LED must be ON in the mode operated by 
ROM. 
The LED must be OFF in the mode operated 
by RAM/Installation mode • mode written in 
ROM. 
P
LC CP
U m
odul
CPU 
[BAT.] LED 
Check that the LED is OFF. The LED must be OFF. 
 (Abnormal if the LED is ON.) 
Refer to  
"QCPU User's 
Manual 
(Function 
Explanation 
/Program 
Fundamentals)".
CPU 
[MODE] LED 
Check that the LED is ON. 
The LED must be ON (green). 
 (Abnormal if the LED is OFF.) 
The LED must be ON (orange) in the 
Installation mode • Mode written in ROM. 
 (Abnormal if the LED is OFF.) 
CPU 
[RUN] LED 
Check that the LED is ON.  The LED must be ON. 
 (Abnormal if the LED is OFF.) 
CPU 
[ERR.] LED 
Check that the LED is OFF.
The LED must be OFF. 
 (Abnormal if the LED is ON or flickers.) 
CPU 
[M.RUN] LED 
Check that the LED is ON 
in RUN state. 
The LED must be ON during operation in 
motion control. 
 (Abnormal if the LED is OFF.) 
Module ind
ication 
LED
 
M
ot
ion CP
U m
odul
CPU 
[BAT.] LED 
Check that the LED is OFF. The LED must be OFF. 
 (Abnormal if the LED is ON.) 
Refer to Section 
2.4.1