Mitsubishi Electronics Q-Series Q170MSCPU ユーザーズマニュアル

ページ / 250
 
 
 
4 - 31 
4   INSTALLATION AND WIRING 
 
4.3.3 Wiring of connector  
Specialised tools are not required for wiring the 24VDC power supply connector and 
forced stop input connector because plugs with spring connection are used. 
 
(1)   Applicable wire size and wire fabrication 
(a)   Applicable wire size 
The applicable wire size for 24VDC power supply connector and forced stop 
input connector are shown below. 
 
Connector 
Type 
Applicable wire size 
24VDC power supply connector 
FKC-2.5/3-ST-5.08 
0.3 t0 2.5mm
2
 (AWG12 to AWG22) 
Forced stop input connector 
FK-MCP1.5/3-ST-3.81 
0.3 t0 1.5mm
2
 (AWG16 to AWG22) 
 
(b)   Wire fabrication 
Strip the wire according to stripped length indicated in the figure below.  
Slide the sheath off the wire and gently twist and straighten the strands. 
When using the wire, be careful not to short with stray strands entering the 
neighbouring poles. Do not use solder on the wire's core as this may lead to 
insufficient contact. 
 
Core
Approx. 
10mm (0.39inch)
Sheath
 
 
1)   Using a ferrule 
A ferrule can also be used to connect with the connector. 
Use the ferrules in the table below for the 24VDC power supply 
connector and forced stop input connector. 
 
Ferrule model  
Connector Wire 
size 
For 1 wire 
For 2 wires 
Crimping tool 
Manufacturer 
AWG16 
AI1.5-10 BK 
AI-TWIN2×1.5-10 BK
24VDC power supply connector 
AWG14 AI2.5-10 
BU 
Forced stop input connector 
AWG21 
AI0.5-10 WH 
— 
CRIMPFOX-ZA3 PHOENIX 
CONTACT
 
• Cut the wire sticking out from the end of the ferrule to 0.5mm 
(0.02inch) or less. 
 
0.5mm (0.02inch)
or less
 
 
• When using a twin ferrule, be sure to insert the wire in a manner that 
will keep the insulation sleeve from interfering with the neighbouring 
poles. Be sure to crimp the ferrule. 
 
Crimping
Crimping