6   INSPECTION AND MAINTENANCE 
 
6.5 Battery 
The battery installed in the Motion controller is used for data retention during the 
power failure of the program memory and latch device.  
The data stored in the RAM built-in Motion controller are shown below. 
• PLC CPU area  : Clock data, Latch devices (L), Devices of latch range, Error history 
and Data in standard RAM 
• Motion CPU area : Programs, Parameters, Motion devices (#), Devices of latch 
range, and Absolute position data   
Special relays (SM51, SM52, SM58 or SM59) of Motion CPU area turn on due to the 
decrease of battery voltage. Even if the special relays turn on, the program and 
retained data are not erased immediately. 
However, if these relays are overlooked, the contents may be erased. 
After relay SM51 or SM58 turns on, replace the battery quickly within the data 
retention time for power failure (3 minutes). 
 
 
POINT 
 
(1)   SM51 or SM58 turns on when the battery voltage falls below the specified 
value, and remains ON even after the battery voltage is recovered to the 
normal value. SM51 or SM58 turns off by power supply on again or reset. 
(2)   After SM51, SM52, SM58 or SM59 turns on, replace the battery quickly. 
• SM51 or SM52 turns on at the battery voltage 2.5V or less. 
• SM58 or SM59 turns on at the battery voltage 2.7V or less. 
(3)   If SM51 turns on, the details for the data of RAM built-in Motion controller 
cannot be guaranteed.  
It is recommended to back-up the data periodically. 
(4)   Whether or not to check the battery of Motion CPU can be set in the system 
basic setting of system setting. If "Perform battery check" is not set, a self-
diagnosis error will not occur and the 7-segment LED "BT1" or "BT2" is not 
also displayed. 
Refer to the "Q173D(S)CPU/Q172D(S)CPU Motion controller Programming 
Manual (COMMON)" for details.