10 - 19 
Chapter 10  High-Level Positioning Control 
 
10.4.2 Condition data setting examples 
The following shows the setting examples for "condition data".   
 
(1)  QD77MS2/QD77MS4 
(a)    Setting the device ON/OFF as a condition 
 
[Condition]  
Device "XC" (Axis 1 BUSY signal) is OFF. 
 
[Da.15] 
Condition target 
[Da.16] 
Condition 
operator 
[Da.17] 
Address 
[Da.18] 
Parameter 1 
[Da.19] 
Parameter 2
01H: Device X 
08H: DEV=OFF
— 
0CH 
— 
 
(b)    Setting the numeric value stored in the "buffer memory" as a condition 
 
[Condition] 
The value stored in buffer memory addresses "800, 801" ("[Md.20] Current 
feed value") is "1000" or larger. 
 
[Da.15] 
Condition target 
[Da.16] 
Condition 
operator 
[Da.17] 
Address 
[Da.18] 
Parameter 1 
[Da.19] 
Parameter 2
04H: Buffer memory 
(2 words) 
04H: 
 
 P1
800 1000  — 
 
(c)    Designating the axis and positioning data No. to be simultaneously started in 
"simultaneous start" 
 
[Condition] 
Simultaneously starting "axis 2 positioning data No.3" 
 
[Da.15] 
Condition target 
[Da.16] 
Condition 
operator 
[Da.17] 
Address 
[Da.18] 
Parameter 1 
[Da.19] 
Parameter 2
05H: Positioning 
data No. 
20H: Axis 2 
selected 
— 
High-order 16 
bits "0003H" 
(Note-1)
 
— 
(Note-1)
 
(Note-1): The setting value of start axis (the axis which executes positioning start) should 
be "0000H".