Omron FQM1-MMA21 ユーザーズマニュアル

ページ / 414
221
Analog Input Functions
Section 7-9
A570
00
Adjustment 
Mode Com-
mand Bits
(Effective only 
when A575 is 
5A5A hex.)
Adjustment 
Enable
Analog Input
OFF: Adjustment disabled.
ON:
Adjustment enabled.
When this bit is turned from 
OFF to ON, the default value 
(offset or gain value) corre-
sponding to the selected I/O 
signal range is transferred to 
Adjustment Value Monitor 
Area (A572 and A573).
User
01
Reserved
02
Analog Output 1
03
Analog Output 2
04 to 06
Reserved
07
Adjustment Mode 
Specifier
OFF: Offset adjustment
ON:
Gain adjustment
User
08 to 11
Reserved
12
Adjustment Value 
Increment
While this bit is ON, the offset or gain value will be 
incremented by one resolution unit each 0.5 s.
Motion 
Control 
Module
13
Adjustment Value 
Decrement
While this bit is ON, the offset or gain value will be 
decremented by one resolution unit each 0.5 s.
14
Adjustment Value 
Clear
OFF to ON: Clears the adjustment data to the fac-
tory defaults.
15
Adjustment Value 
Set
OFF to ON: Reads the present value in the 
Adjustment Value Monitor Area (A572 
and A573) and saves this value to 
flash memory. This adjustment value 
will be used for the next normal mode 
operation.
A571
00
Adjustment 
Mode Status
Adjustment Oper-
ation Error
ON when an operational error has been made, 
such as turning ON both the Analog Input and Ana-
log Output 2 Adjustment Enable Bits at the same 
time.
Motion 
Control 
Module
01 to 14
Reserved
15
Adjustment Mode 
Started
ON during adjustment mode operation (when A575 
contains 5A5A hex). 
A572
00 to 15
Adjustment 
Mode Monitor
(Effective only 
when A575 is 
5A5A hex.)
Used for Analog 
Input and Analog 
Outputs 1/2
Setting Offset Moni-
tor
The values in 
these words 
can be over-
written 
directly, with-
out using the 
Adjustment 
Value Incre-
ment/Decre-
ment Bits.
−10 to 10 V: 
FE0C to 
01F4 hex
• 0 to 10 V, 0 
to 5 V, 1 to 
5 V: FF38 to 
00C8 hex
Motion 
Control 
Module or 
User
A573
00 to 15
Gain Value Monitor
−10 to 10 V: 
1194 to 
157C hex
• 0 to 10 V, 0 
to 5 V, 1 to 
5 V: 0ED8 to 
1068 hex
A574
00 to 15
Analog Inputs
Number of Average 
Value Samples in 
Adjustment Mode
Indicates the number of val-
ues to be averaged to obtain 
the Offset/Gain Value Moni-
tor values in adjustment 
mode. The number of sam-
ples can be set between 
0000 and 0040 hex (0 to 64). 
Set this parameter before 
turning ON the Adjustment 
Enable Bit.
User
A575
00 to 15
Adjustment Mode Password
5A5A hex: Adjustment mode enabled.
Other value: Adjustment mode disabled.
User
Word
Bits
Function
Settings
Controlled 
by