Section 8: Guidelines for
Locating Smoke Detectors
Research has shown that all hostile fires in homes gen-
erate smoke to a greater or lesser extent. Experiments 
with typical fires in homes indicate that detectable 
quantities of smoke precede detectable levels of heat in 
most cases. For these reasons, smoke alarms should be 
installed outside of each sleeping area and on each sto-
rey of the home.
The following information is for general guidance only 
and it is recommended that local fire codes and regula-
tions be consulted when locating and installing smoke 
alarms.
It is recommended that additional smoke alarms beyond 
those required for minimum protection be installed. 
Additional areas that should be protected include: the 
basement; bedrooms, especially where smokers sleep; 
dining rooms; furnace and utility rooms; and any hall-
ways not protected by the required units.
On smooth ceilings, detectors may be spaced 9.1m (30 
feet) apart as a guide. Other spacing may be required 
depending on ceiling height, air movement, the pres-
ence of joists, uninsulated ceilings, etc. Consult National 
Fire Alarm Code NFPA 72, CAN/ULC-S553-M86 or other 
appropriate national standards for installation recom-
mendations. 
Do not locate smoke detectors at the top of peaked or 
gabled ceilings; the dead air space in these locations 
may prevent the unit from detecting smoke.
Avoid areas with turbulent air flow, such as near doors, 
fans or windows. Rapid air movement around the 
detector may prevent smoke from entering the unit.
Do not locate detectors in areas of high humidity.
Do not locate detectors in areas where the temperature 
rises above 38
o
C
 
(100
o
F) or falls below 5
o
C (41
o
F).
Smoke detectors should always be installed in accor-
dance with NFPA 72, the National Fire Alarm Code. 
Smoke detectors should always be located in accor-
dance with:
• Paragraph 2-2.1.1.1 of NFPA 72, Chapter 2: ‘Smoke 
detectors shall be installed outside of each separate 
sleeping area in the immediate vicinity of the bed-
rooms and on each additional storey of the family 
living unit, including basements and excluding crawl 
spaces and unfinished attics. In new construction, a 
smoke detector also shall be installed in each sleep-
ing room’.
Paragraph 2-2.1.1.2 of NFPA 72, Chapter 2: ’Split 
level arrangement: Smoke detectors are required 
where shown. Smoke detectors are optional where 
a door is not provided between living room and 
recreation room’.