Bosch D9112B ユーザーズマニュアル

ページ / 96
D9112B | Program Entry Guide | 1.0  Panel Wide Parameter 
EN | 21 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
P## Area Assign 
Default: 
Selection: 
1 to 8 
Assign each installed printer to an area of the 
D9112. This allows the proper routing of events as 
determined by the Printer Scope. Assign printers 
with Panel Wide scope to Area 1. Assign printers 
with Account scope to an area within the account 
number you want to record. 
System events such as power supervision, passcode 
changes, RAM events and such, are only sent to the 
printer assigned to AREA 1. To record these events, 
make sure a printer is assigned to Area 1 and that 
PRT Non Alrm
 is programmed YES for that 
printer. 
P ## Supervision 
Use this prompt to determine if any responses are 
generated when the printer at this address fails. See 
the D9131 Printer Interface Operation and Installation 
Guide
 for conditions that are supervised. 
Default: 
No 
Selection: 
Yes or No 
Yes 
No report or local annunciation if this 
printer fails. 
No 
Send an 
SDI Fail
 report identifying the 
printer address (17, 18, or 19) to the 
receiver if this printer fails. (Program 
Diagnostic
 reports for a primary 
phone destination in the Phone Routing 
Worksheet
). Sends a message to all other 
printers as non-alarm events. Display 
SERVC PRINTER
 at all command 
centers. A relay can be assigned to 
indicate printer trouble (see Relay 
Assignments
). 
P## Prt Points 
Point events include every event that can be 
generated by a point. Events include all of the events 
listed in the Fire Alarm/Restoral, Fire Tbl/Rest, 
AlarmRest/Cancel, and Trouble logs shown in the 
Phone Routing Worksheet
Default: 
Yes 
Selection: 
Yes or No 
Yes 
Print point events according to the 
Printer Scope and Area Assignment. 
All point events are printed on the 
local printer regardless of how many 
points are programmed. 
No 
Do not print any point events. 
P ## Prt O/C 
O/C events are all of the events listed in the 
Opening and Closing log shown in the Phone Routing 
Worksheet
Default: 
Yes 
Selection: 
Yes or No 
Yes 
Print Opening and Closing events 
according to the Printer Scope and 
Area Assignment. All arming and 
disarming events are printed on the 
local printer regardless of the 
programming of any other prompts 
associated with openings and closings. 
No 
Do not print any Opening and Closing 
events.  
P## Prt Non Alrm 
Non-Alarm Events are all of the events except Point 
events and Opening/Closing events. Non-Alarm 
events include all of the events listed in the 
Test/Status, Diagnostic, Relay, Skeds, RAM, 
Power/Phone, and Service logs shown in the Phone 
Routing Worksheet
. Information from 
Expanded Test
 
reports is not printed when the 
Test
 report is 
generated. 
Default: 
Yes 
Selection: 
Yes or No 
Yes 
Print non-alarm events according to the 
Printer Scope and Area Assignment. 
No 