Bosch D9112B ユーザーズマニュアル

ページ / 96
D9112B | Program Entry Guide | 1.0  Panel Wide Parameter 
EN | 9 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
Default: 
Blank 
Selection: 
Up to 24 characters (do not enter [SPACE]) 
0 - 9 
Numbers zero through nine 
3 sec. pause 
7 sec. dial-tone detect. 
# or * 
The same as pressing this key on a telephone keypad when manually dialing. For example, you may 
need an asterisk (*) to access your long distance service. Do not use these characters when pulse 
dialing. 
Blank 
Panel dials no phone number.  
Programming this item 
Blank does not disable phone routing. To disable reporting to this phone see 
Phone Routing
Phone 2 
Default: 
Blank 
Selection
Up to 24 characters (do not enter 
[SPACE]) 
 (See explanation of Phone 1.) This number is 
“Phone 3,” referenced in Phone Routing Parameters
Phone 3 
Default: 
Blank 
Selection
 
Up to 24 characters (do not enter 
[SPACE]) 
 (See explanation of Phone 1.) This number is 
“Phone 3,” referenced in Phone Routing Parameters
Phone 4 
Default: 
Blank 
Selection: 
Up to 24 characters (do not enter 
[SPACE]) 
 (See explanation of Phone 1.) This number is 
“Phone 4,” referenced in Phone Routing Parameters
Modem Format 
The central station receiver format for transmitting reports, 
Modem Format
 provides many reporting advantages 
over the BSFK format (see the D6500 Report Directory for more information about the effect of reporting 
formats). 
Default: 
Yes 
Selection
 
Yes or No 
Yes 
Modem II (requires Bosch Security Systems D6500 Receiver with MPU EPROM version 6.00 or 
higher and Line EPROM version 6.00 or higher) 
Modem II format reports identify points as 001 through 135 and passcode User ID codes as 00 
through 99 at the D6500 receiver (unless 
Point/User Flag
 is programmed YES, see the next prompt). 
When reporting point events, Modem II also sends point text to the D6500 as programmed in Point 
Assignments
No 
BFSK (2300 Hz or 1400 Hz acknowledgment tone). 
Basic reporting functions are available, but reporting options are limited to account opening and 
closing (see 
A# Acct O/C
 and 
A# Area O/C
), users are identified by only one digit as programmed 
in Point Assignments 
P### BFSK/Relay