Bosch 3.5 ユーザーズマニュアル

ページ / 498
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 10 | Events
en | 413
51
Overview
51.1 Introduction
51.2 General 
events
General events contain information about special 
situations. For example, the connection of a unit to the 
system. See chapter 52 for a list of all general events.
51.3 Call 
events
Call events contain information about calls in the 
system. For example, the start of a call. See chapter 53 
for a list of all call events.
51.4 Fault 
events
51.4.1 Introduction
Fault events contain information about faults in the 
system. For example, an overload of a power amplifier. 
See chapter 54 for a list of all fault events.
51.4.2 Status
Each fault event has a status (see table 51.1).
51.4.3 Acknowledging fault events
51.4.3.1
Introduction
New fault events can be acknowledged:
Using the network controller (see section 51.4.3.2).
Using control inputs or keys (see section 51.4.3.3).
Using the open interface (see section 51.4.3.4).
Using  the  Logging Viewer (see chapter 57).
51.4.3.2
Network controller
New fault events can be acknowledged using the 
Faults... menu of the network controller (see 
section 5.6.5). Using this menu it is possible to 
acknowledge individual fault events as well as all new 
fault events in the system.
51.4.3.3
Control input or key
New fault events can be acknowledged using control 
inputs or keys to which an Acknowledge/Reset action has 
been assigned (see section 47.3.23). However, such a 
control input or key acknowledges all new fault events 
in the system. It is not possible to acknowledge 
individual faults using a control input or key.
51.4.3.4
Open interface
New fault events can be acknowledged using the open 
interface (see the Open Interface Programming 
Instructions).
51.4.4 Resolving fault events
Before acknowledged fault events can be reset, they first 
must be resolved. Most fault events are automatically 
resolved by the system when the fault situation no 
longer exists. Others need to be resolved manually. 
Manual resolving is needed for faults whose presence is 
not checked again after they occurred (for example, an 
amplifier overload). After solving the problem, the fault 
status of these fault events must be manually set to 
Resolved. This is done by resetting the fault, after which 
the system checks the presence of the fault again. If the 
fault is not present anymore, the status of the fault event 
is set to Resolved and then to Reset. If the fault is still 
present, a new fault event is created.
table 51.1 Fault event statuses
Status
Description
New
The fault event is a new fault 
event. All fault outputs are 
activated.
Acknowledged
The new fault event is 
acknowledged. If all faults in the 
system have been 
acknowledged, all fault alarm 
buzzer outputs are deactivated.
Resolved
The acknowledged fault event is 
resolved.
Reset
The resolved fault event is reset. 
If all faults in the system have 
been reset, all  Fault alarm 
indicator outputs are 
deactivated.
Note
A fault output is a control output that has been 
configured as an Fault alarm buzzer or as a 
Fault alarm indicator (see table 43.6).
Note
When all faults are acknowledged, the Fault 
alarm buzzer outputs are deactivated.