Safety instructions 
SDC / DHC  
12 EN2H-0221GE51 
R0808 
2.2.1 Power 
supply 
Do not disconnect the controller from the mains supply! 
The battery for saving all individualised data is otherwise 
unnecessarily strained. The frost-protection function of the 
controller is deactivated. 
 
2.2.2 Connection 
conditions 
All electrical connection work may only be carried out by qualified 
personnel! 
 
2.2.3 Cable 
cross-sections 
1.5 mm
2
 for all cables carrying 230 V (power supply, burner, 
pumps, actuator). 
0.6 mm
2
 for bus cables (recommended type J-Y(St)Y 2 x 0.6). 
0.5 mm
2
 for sensors, selectors and analog signal cables. 
 
2.2.4 Maximum 
cable 
lengths 
Sensor, selector and analog inputs 
We recommend using cables no longer than 200 m. Longer 
connection lines could be used, but increase the risk of 
interference. 
 
Relay outputs 
Unlimited cable length. 
 
Bus connections 
Max. length of 100 m from the first bus subscriber to the last one 
(incl. wall modules). 
 
2.2.5 Cable 
installation 
Install cables for sensors apart from the cables carrying 230 V! 
Branch boxes in the sensor cable must be avoided!