Hydraulic Components 
SDC / DHC  
130 EN2H-0221GE51 
R0808 
The boiler temperature is maintained according to the set 
minimum temperature, independent of demands or deactivating 
control modes. 
 
5.2.4 "DHW" menu, pg. 77 
 
7.1.3 Maximum 
temperature 
limit heat generator  
In order to protect the heat generator against overheating, the 
controller is equipped with an electronic maximum temperature 
limit. It shuts off the burner if the temperature in the heat 
generator exceeds the limit value. 
The burner is switched on again if the temperature in the heat 
generator falls below the limit value by half of the burner switching 
differential plus 2 K. 
 
5.2.4 "DHW" menu, pg. 77 
 
7.1.4  Heating circuits minimum temperature limit  
•  If the boiler temperature BT
actual
 is less than or equal to the 
parameter setting 27 (BT
min
 - HC), the heating circuit pumps 
switch off (DHCP, SFP, MCP). The mixed heating circuit 
valves close. 
•  If BT
actual
 is greater than BT
min 
- HC + SC
min 
- HC, the heating 
circuit pumps and mixed heating circuit valves are enabled 
again. 
 
7.1.5  Heat generator sensor control mode  
There are various ways in which the heat generator can react to a 
malfunction of the heat generator sensor: 
 
Burner switch-off in case of a faulty heat generator sensor 
A fault message appears in case of a short-circuit or interruption 
of the sensor; the burner will be switched off. 
External burner switch-off 
In case of the interruption of the sensor the burner is switched off 
without a fault message. It is used, for example, for external 
See also
Function
See also
Function