Hydraulic Components 
EN2H-0221GE51 R0808 
145 
7.2.1  On/Off operation of the district heating valve  
To always ensure a minimum flow so that the heat meter can 
work precisely, pure on/off switching is provided in low load mode. 
Code 03 is suitable for this function as shown in the following 
diagram. 
 
100 %
100 %
0 %
x
y
a
 
 
a Minimum 
travel 
y Controller 
output 
x Valve 
travel 
   
 
Para-
meter
 
Designation  Range   Presetti
ng 
Step 
Unit 
03 Minimum 
travel 
0 ... 50  10 
 
Should the secondary flow temperature controller output fall 
below the settable minimum travel in % (code 03), two-step 
operation begins and the valve is closed. The valve remains 
closed until the internal controller output reaches 10% again. If a 
10% controller output is reached, the valve opens again to the 
minimum travel. If the controller output drops below 10% again, 
the valve closes again and the cycle starts from the beginning. 
This means that whenever there are demands of up to 10% on 
the heat generator the valve is operated in On/Off mode and the 
secondary flow temperature is controlled this way. 
 
7.2.2 Continuous 
heat 
exchanger valve control  
If the output of the secondary flow temperature controller rises 
above 10%, the PI controller controls the secondary flow